Sensing input
| 3-ph/2-ph - 220/230/240/380/400/415 volts for 50 Hz 3-ph/2-ph - 208/240/277/380/416/440/480 volts for 60 Hz
|
Voltage range high
| 300V to 530V
|
Voltage range low
| 180V to 310V
|
Droop
| 1 and 5A AC in U phase
|
Droop range
| 8% droop at 0.8 PF
|
PMG input power
| Continuous: 240V RMS +10% Momentary 5 s: 240V RMS + 30 Up to 240 Hz
|
AREP+ input power
| Continuous: 250V peak+10% Momentary 10 s: 350V peak +5% - Up to 75 Hz
|
Excitation current
| 6A DC continuous 9A for 5 seconds (short-circuit operation)
|
Regulation
| ± 0.5% at AVR sensing terminals
|
Maximum excitation limit
| 6A DC (factory setting)
|
Maximum excitation limit delay
| 30 sec. (factory setting)
|
Under frequency protection
| 48.5 Hz/58.5 Hz for 50 Hz/60 Hz operation
|
Slope
| 1.2X (120%) V/Hz
|
Remote potentiometer
| 1 kOhm for ± 10% adjustment
|
Accessory Input
| ± 4.5V DC for ±15%
|
Temperature range
| -25ºC to +70ºC
|
Storage temperature range
| -40ºC to +80ºC
|
Thermal drift
| 0.5% for 20ºC change
|
Fuse
| FST 10A 250V
|