Diesel Genset Features P.F=0.8 3Phase |
Generating Set Performance | | 50Hz |
Service | | P.R.P | Standby |
Rated output | kVA | N.A | 688 |
Active power output | kW | N.A | 550 |
Rated Speed | r.p.m | 1500 |
Standard Voltage | V | 400/230 |
Voltage available | V | 380/220 - 415/240 |
Perforemance data refer to Standard Reference Conditions of ISO 8528:+25ºC,100m ALT,relative humidity 30% | |
Power reduction acc.to DIN ISO 3046 Standard values:Above 100m ALT approx.1% per 100m.Above 25ºC(77ºF) approx.4% per 10ºC(50ºF). | |
Considering cos phi=0.8 |
|
Prime Mover Performance 1500 r.p.m |
SERVICE | | P.R.P | Standby |
Rated output | KW | N.A | 610 |
Manufacturer | | Cummins |
4 stroke Diesel Engine - Injection type | | Direct |
Aspiration type | | Turbocharged&Air-Air Cooled |
Cylinders,number and arrangement | | 6 -L |
Bore×Stroke | mm | 159X159 |
Total Displacement | L | 19 |
Cooling system | | Water |
Emission Certification | | N.A |
Compression ratio | | 13.9:1 |
Specific fuel consumption(Standby power) | L/h | 157 |
Specific oil consumption(at full load) | % | <0.1 |
Total coolant capacity | L | 118,5 |
Fuel System | Type | Direct Injection Cummins PT(E) |
| | | | | | | | | | |
1.P.R.P. Prime Power - ISO 8528:PRIME POWER is the maximum power available during a variable power sequence, which may be run for an unlimited number of hours per year, between stated maintenance intervals.The permissible average power output during a 24 hours period shall not exceed 80% of the prime power.10% overload available for governing purposes only. |
2.Max Standby power -ISO 3046 Fuel Stop power:Power available for use at variable loads for limited annual time (500h), within the following limits of maximum operating time: 100% load 25h per year ,90% load 200h per year. No overload available. Applicable in case of failure of the main in areas of reliable electrical network. |
| |
Synchronous Generator GTL |
Model | | K500G4 |
Poles | num | 4 |
Winding Conections (standard) | | Star-serie |
Insulation | class | H |
Enclosure(according to IEC-34-5) | | IP23 |
Phases | | 3+N |
Votage Regulators | | A.V.R (SX440) |
Steady voltage precision | | within±1.0% from no load to full loading with cosΦ=0.8-1.0 |
Alternator used by GTL Gensets meet the requirements of following Standard:BS5000,VDE0530,NEMA MG1-32,IEC34,CA C22.2-100,AS1359 |
| | | | | | | | | | |
Generationg Set Installation Data 1500 r.p.m |
EXHAUST SYSTEM |
Exhaust Gas Temperature at full load | ºC | 446 |
ºF | 834,8 |
Exhaust gas flow | L/s | 2478 |
Maximum allowed back pressure | Kpa | 10 |
AIR REQUIREMENT |
Air requirement for combustion at 100% load/rated speed | L/s | 850 |
ft3/min(CFM) | 1800,0 |
ELECTRIC STARTING SYSTEM |
Standard Battery Charging System | A | 35 |
Minimum Recommended Battery Capacity-Cold Soak @ 0 °F (-18 °C) | CCA | 900 |
Auxiliary voltage | V | 24 |
LUBRICATION SYSTEM |
Lube oil system including sump,filters,etc. | L | 50 |