Load Break Switch, Lbs, Sf6 Disconnect Switch

Min.Order: 1
Product origin: Xiamen, Fujian, China
Infringement complaint: complaintComplaint
US$ 550

Description

General:
GSC-12 an indoor high-voltage SF6 load switch, an switchgear wi ththe rated voltage of  12kV/24kV, adopted with SF6 gas as an arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off andto-ground, and is characteristic in its small volume, its convenient installation and operation and itsthe great adaptability with surroundings. 
GSC-12 of an indoor high-voltage SF6 load switch and   GSC-12D of SF6 load switch plus fuse combination canfunctionto protect and control the electric equipments for power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation. 
GSC-12 of an indoor high-voltage SF6 load switch and   GSC-12D load switch plus fuse combination are complied withthe standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc.. 
Service environment:
   a) Airtemperature 
      Maximumtemperature: +40ºC; Minimumtemperature:-5ºC
    b) Humidity 
       Monthly average humidity 95%; Daily average humidity 90%. 
   c) Altitude above sea level 
       Maximum installation altitude: 2500m 
   d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 
   e) Nofrequent violent shake
++++Main technical specifications:

 No

Item

  Unit 

 Parameter

 1

Rated voltage

  kV

  12 

 2

 Rated frequency

    Hz 

  50/60

 3 

 Rated current 

 A 

 630/800

 4 

                                                        wet 

1min Power frequency  withstand voltage
                                                        dry 

 kV 

38

 

48

 5

 Lightning impulse withstand voltage

   kV 

  75

 6 

 Rated short circuit breaking current (peak)

  kA

  80 

 7

  Rated activeload and close circuit breaking current

  A 

  63 

 8

  Rated transferring current 

 A 

  1700

 9

  Rated short circuit making current (peak)

 kA

   80 

 10

  Rated cable(line) charging breaking current 

  A

  50 and 10

 1 1 

  Cable charge breaking current in earthing fault 

 A 

 20 

 12

 Rated withstand current (peak)

 kA

 80

 13 

 Short time withstand current (2s)

 kA

  31.5

  14

          Mechanism life 

 times 

  5000 

       
Note: For short circuit breaking and peak current isbased on Fuseplus combination.
Scroll to Top