Indoor High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuses

Min.Order: 2
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 530 ~ 850

Description



 

FN18 series Indoor High Voltage Load Break Switch Nalf Air Insulation Switch Breakers Fuses

FN18 is a general purpose, three-pole, load break switch that offers switchgear owners and assemblers the advantages of an advanced interrupting technology and proven, dependable performance in a compact design. The switch is available to switchgear assemblers as a building block for metal-enclosed and pad-mounted switchgear applications in ratings from 12-40.5 kV.
The standard FN18 switch includes a heavy-duty steel frame with stand-off insulators, a unique puffer-type arc extinguishing system, an operating mechanism and current-carrying components, including blade-type interrupters with cast hinges and jaw connectors.
Optional accessories and features include a variety of operating handles, a motor operator, auxiliary switches, a shunt trip device, fuse bases, mechanical fuse tripping, grounding switches, mechanical door interlocking and key interlocking.

FN18 series indoor high-voltage load switch has the advantages of easy design, operation, compact structure, small volume, full function, light weight, fast breaking and closing speed and high reliability. It is suitable for AC 50Hz, rated voltage 12kV, 24kV, rated current 630A and three-phase distribution system, especially for city network construction and renovation projects, high-rise buildings, ring network power supply of public facilities, and is an ideal product for box-type substation and transformer protection.

Technical parameter
 

Rated voltageUnit12kV17.5kV24kV36kV40.5kV
Rated currentA40063012504006301250400630125063080010006308001000
Max. rated currentA400630125040063012504006301250630800800630800800
Short circuit making capacityKA peak6750505050
Peak withstand currentKA peak8282826666
Short time current1 sec.KA eff

31.5

25

20

31.5

25

20

31.5

25

20

31.5

25

31.5

25

31.5

25

25

25

16

25

25

16

31.5

25

16

252525252525
2 sec.
3 sec.
Mainly active load breaking capacity 21 (test duty 1 and, IEC 60265-1( 265))A400630125040063012504006301250630800630800630800
Mainly capacitive breaking capacity (test duty 4, IEC 60265-1 (IEC 265))A15045805050
Mainly inductive breaking capacity cosφ=0.15A1616161616
Max. breaking capacity in co-operation with fuses IEC 62271-105(IEC 420 1990-11)A16001600 16001600 900900 300300300300300300

Power frequency withstand voltage 50 Hz 1 min.

-to earth and between poles

-across isolating distance

kV

42

45

45

60

55

70

80

88

95

120

Impulse withstand voltage 1.2/50 μs

- to earth and between poles

- across isolating distance

kV

75

85

95

110

125

145

170

195

190

220

Pole distancemm150, 170, 210170, 210170, 235, 275360360

Max. operating torque at:

-closing K/A mech.

-opening K/A mech.

Nm115-120 Nm
K-mech.120 Nm/A-mech. 3Nm
80-100 Nm
K-mech.80-100 Nm
Operating angle on the shaftdegree130120
Opening timems40-6060



 

 

Structure




Scroll to Top