Model Name | Input | Output | Perforation Hole Size(mm) | |
AC Current | DC Current | DC Voltage | ||
BA05-AI/I | 0~(0.5~10)A | 4~20mA/0~20mA | / | φ5 |
BA05-AI/V | 0~(0.5~10)A | / | 1~5V/0~5V | |
BA10-AI/I | 0~(8~50)A | 4~20mA/0~20mA | / | φ10 |
BA10-AI/V | 0~(8~50)A | / | 1~5V/0~5V | |
BA20-AI/I | 0~(40~200)A | 4~20mA/0~20mA | / | φ20 |
BA20-AI/V | 0~(40~200)A | / | 1~5V/0~5V | |
BA50-AI/I | 0~(60~600)A | 4~20mA/0~20mA | / |
|
BA50-AI/V | 0~(60~600)A | / | 1~5V/0~5V | |
BA50L-AI/I | 0~(0.1~1)A | 4~20mA/0~20mA | / | |
BA50L-AI/V | 0~(0.1~1)A | / | 1~5V/0~5V |
Wiring Terminals Overview of BA Series Current Transducer
Cable Wiring of BA Series Current Tranducer with DC Current Output
Cable Wiring of BA Series Current Tranducer with DC Voltage Output
Model Name | Outline Size (mm) | |||||
W | H | Φ | M | N | L | |
BA05-AI/I&BA05-AI/V | 35 | 69 | 5 | 62.5 | 76 | 22.5 |
BA10-AI/I&BA10-AI/V | 35 | 74 | 9.5 | 62.5 | 76 | 22.5 |
Technical parameter
Item | Description |
Auxiliary Power Supply | DC 12V (range of 10~15V) or DC 24V (range of 18~30V) |
Accuracy Class | 0.5% |
Load Resistance (Output) | Current Output: ≤500Ω; Voltage Output: ≤1000Ω |
Response Time | ≤350ms |
Temperature | Operation Temp.: -10ºC~+55ºC; Storage Temp.: -40ºC~+80ºC |
Temperature Coefiicient | ≤200ppm/ºC |
Humidity | ≤90% |
Altitude | ≤2500m |
Installation | 35mm DIN Rail or Screw fixed |
Standard | CE/TüV |