Model | 3RWG90KM30 | 3RWG150KM30 | 3RWG180KM30 | 3RWG240KM30 | 3RWG270KM30 |
Capacity | 90KVA | 150KVA | 180KVA | 240KVA | 270KVA |
Type of power module | GM30 |
Input mode | 3 Phase 4 Wires+ Ground |
Input voltage(Vac) | 380V/220V±20%,400V/230V±20%,415V/240V±20% |
Input Frequency(HZ) | 50Hz±10%,60Hz±10% |
Input PF | ≥0.99 |
Battery voltage(Vdc) | ±240 |
Charge Time | 10hs (2hs backup battery capacity) |
Battery quantity(Pcs) | 32-48 can be adjusted |
UPS Power Factor | 1.0 |
Output Voltage(Vac) | 380/220V,400/230V,415/240V |
Output Frequency(HZ) | 50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2% 60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2% |
Output voltage Stability | ±1%(Static);±2%(Load change from 0 ~ 100% ) |
Efficiency (AC mode @ full loads) | ≥94% |
Output voltage recovery time | <20ms(Load change from 0 - 100% ) |
Overload | Rated load 125% ,runs 10mins |
Communication function | RS232/RS485/422/ dry contact/TCP/IP Expansion cards |
SMMP(optional) | Can be network monitored by SNMP adapter |
Parallel function | Yes(for optional) |
Alarm | Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection |
Working Environment Temperature | -5ºC~40ºC |
IP Class | IP31 |
Cooling | Speed controlled air cooling |
Noise(dB) | ≤55dB(Within 1 meter) |
Structure | 19 inches Standard |
Monitor Management System | UP Supervisor |
Display | Touchable screen LCD/LED |
Dimension(W*D*H) | 600×800×1200 | 600×800×1600 | 600×800×1600 | 600×800×2000 | 600×800×2000 |
Weight (Kg) | 120KG | 140KG | 160KG | 200KG | 250KG |