Model | AIM-M10 | ||
auxiliary power supply | |||
Voltage | DC24V( fluctuation range ±25%) | ||
Max power consumption | <3VA | ||
insulation monitoring | |||
Insulation resistance measuring range | 10~999kΩ | ||
Relative percentage accuracy | 0~±10% | ||
Alarm value range | 50~999kΩ | ||
Response time | <2S | ||
Measuring voltage | <12V | ||
Measuring current | <50μA | ||
Current monitoring | |||
Measuring range | 2.1~50A | ||
Alarm value range | 5~50A | ||
Measuring accuracy | class 5 | ||
Display | Digital and percentage display | ||
Temperature monitoring | |||
thermal resistor | PT100 | ||
Measuring range | -50ºC~+200ºC' | ||
Alarm value range | 0ºC~+200ºC' | ||
Alarm output | |||
Output type | 2 channel relay output(unable to program) | ||
Contact rating | AC 250V/3A DC30V/3A | ||
Environment | |||
Working temperature | -10ºC~+55ºC' | ||
Storage temperature | -20ºC+70ºC' | ||
Relative humidity | 5%~95%,non-condensing | ||
Altitude | ≤2500m | ||
Communication | |||
one channel RS485,MODBUS-RTU 1 channel CAN interface,user-defined | |||
Rated impulse voltage/pollution class | |||
4KV/III | |||
EMC and electromagnetic radiation | |||
In accordance with IEC1326-2-4 |
name | model |
Insulation monitor | AIM-M200 |
Power module | DR-60-24 |
Isolation transformer | AITR8000 |
Current Transformer | AKH-0.66P26 |
test signal generator | ASG150 |
insulation fault locator | AIL150-4 |
centralized remote alarm indicator | AID150 |