Technical Specifications
Rated System Voltage (kV) | Type | Section Length (mm) | Arcing Distance (mm) | Creepage Distance (mm) | Coupling Size | Specified Cantilever Load (kN) | Specified Tensile Load (kN) | Lightning Impulse Withstand Voltage (kV) | Power Frequency Withstand Voltage (kV) | |
Dry | Wet | |||||||||
35 | FSP-35/0.4-1 | 670 | ≥420 | 810 | 16 | 0.4 | 70 | 230 | 106 | 95 |
35 | FSP-35/0.4-2 | 670 | ≥420 | 1015 | 16 | 0.4 | 70 | 230 | 106 | 95 |
35 | FSP-35/0.4-3 | 730 | ≥480 | 1350 | 16 | 0.4 | 70 | 230 | 106 | 95 |
66 | FSP-66/0.4-1 | 870 | ≥620 | 1650 | 16 | 0.4 | 70 | 410 | 206 | 185 |
66 | FSP-66/0.4-2 | 940 | ≥690 | 1920 | 16 | 0.4 | 70 | 410 | 206 | 185 |
66 | FSP-66/0.4-3 | 1000 | ≥750 | 2450 | 16 | 0.4 | 70 | 410 | 206 | 185 |
66 | FSP-66/0.8-1 | 870 | ≥620 | 1650 | 16 | 0.8 | 70 | 410 | 206 | 185 |
66 | FSP-66/0.8-2 | 940 | ≥690 | 1920 | 16 | 0.8 | 70 | 410 | 206 | 185 |
66 | FSP-66/0.8-3 | 1000 | ≥750 | 2450 | 16 | 0.8 | 70 | 410 | 206 | 185 |
110 | FSP-110/0.4-1 | 1340 | ≥1040 | 3150 | 16 | 0.4 | 70 | 550 | 356 | 230 |
110 | FSP-110/0.4-2 | 1440 | ≥1140 | 3520 | 16 | 0.4 | 70 | 550 | 356 | 230 |
110 | FSP-110/0.8-1 | 1340 | ≥1040 | 3150 | 16 | 0.8 | 70 | 550 | 356 | 230 |
110 | FSP-110/0.8-2 | 1440 | ≥1140 | 3520 | 16 | 0.8 | 70 | 550 | 356 | 230 |
110 | FSP-110/0.8-3 | 1800 | ≥1500 | 4370 | 16 | 0.8 | 70 | 550 | 356 | 230 |
110 | FSP-110/1.3-1 | 1600 | ≥1300 | 4350 | 16 | 0.8 | 70 | 550 | 356 | 230 |
220 | FSP-220/0.8-1 | 2150 | ≥1850 | 5040 | 16 | 0.8 | 70 | 1000 | 440 | 395 |
220 | FSP-220/0.8-2 | 2350 | ≥2050 | 6340 | 16 | 0.8 | 70 | 1000 | 440 | 395 |
220 | FSP-220/1.3-1 | 2470 | ≥2170 | 7040 | 16 | 0.8 | 70 | 1000 | 440 | 395 |
220 | FSP-220/1.3-2 | 3090 | ≥2790 | 8730 | 16 | 0.8 | 70 | 1000 | 440 | 395 |
330 | FSP-330/0.8-1 | 2930 | ≥2630 | 7260 | 16 | 0.8 | 70 | 1425 | 630 | 570 |
330 | FSP-330/0.8-2 | 3150 | ≥2850 | 9240 | 16 | 0.8 | 70 | 1425 | 630 | 570 |
330 | FSP-330/0.8-3 | 3350 | ≥3050 | 10 560 | 16 | 0.8 | 70 | 1425 | 630 | 570 |
Order Information: 1. Voltage grade; 2. Specified mechanical load; 3. Creepage distance; 4. Power frequency withstand voltage; 5. Lightning impulse withstand voltage;6. Insulation distance; 7. Coupling type; Ps. Different design could be supplied as customer requirements |