12kw R32 Full DC Inverter a+++ Split Air to Water Heat Pump Water Heater for Heating Cooling and Hot Water

Min.Order: 1
Product origin: Foshan, Guangdong, China
Infringement complaint: complaintComplaint
US$ -1

Description
R32 Full DC Inverter a+++ Split Heat Pump Water Heater for Heating Cooling and Hot Water
Features:

1.Hot water up to 65ºC,suitable for underfloor/radiator heating/fan coil

2.can work stable at ambient temperature -25C to 45C

3.E-Heater,diverter valve and water pump can be inclueded

4. A+++ Energy Rating Level

5.Full inverter system,Stable and efficient performance.

6.R32 System,environment friendly

7.Application Scope:Hotels,clubs,hospitals,villas and any place in need of air conditioning,heating and hot water

8.With Wifi App control

Installation Diagram:
 


Technical Parameter
Market model WW08V-SWW10V-SWW12V-SWW14VM-S
Heating1Output CapacitykW3.40~8.653.70~10.304.95~12.465.92~14.94
Input Power kW0.59~1.650.62~2.050.90~2.481.15~3.20
COP-5.23~5.725.02~5.905.03~5.504.67~5.12
Input CurrentA2.82~7.922.96~9.814.31~11.855.50~15.3
Heating2Output CapacitykW3.43~7.773.90~9.844.37~12.435.18~14.30
Input Power kW0.91~2.411.01~3.121.21~3.951.33~4.69
COP-3.23~3.803.15~3.813.15~3.613.05~3.89
Input CurrentA2.56~11.524.83~14.935.78~18.896.36~22.45
Heating3Output CapacitykW4.11~10.375.10~13.256.25~14.637.52~16.57
Input Power kW0.74~2.280.94~13.731.14~3.121.37~3.56
COP-4.55~5.564.61~5.424.69~5.464.66~5.47
Input CurrentA3.54~10.914.50~12.495.45~14.936.55~17.03
Cooling4Output CapacitykW3.04~7.573.82~8.215.05~11.456.02~12.31
Input Power kW0.94~2.751.18~3.021.54~4.131.87~4.53
EER-2.75~3.232.72~3.252.77~3.282.73~3.22
Input CurrentA4.50~13.155.64~14.457.37~19.768.95~21.67
Power Supply V/PH/HZ220-240V/1/50Hz
ErP level(35ºC)-A+++A+++A+++A+++
ErP level(55ºC)-A++A++A++A++
Water Side Heat Exchanger -Plate heat exchanger
Display controller -LCD touch screen
Backup heater (Optional) kW3kW 
Expansion vessel-5L
Refrigerant Type -R32
Max Water Temperature
 (without backup heater)
ºC60
Working Ambeint TemperatureºC-25~43
Water connection inchG1-1/4
Sound pressure Level @1m outdoor unitdB(A)50505253
indoor unitdB(A)27272727
Net Dimension (L*W*H) outdoor unitmm995*410*800995*410*8001065*410*9601065*410*960
indoor unitmm475*220*800475*220*800475*220*800475*220*800
 
Market model WW14VT-SWW16V-SWW18V-SWW20V-SWW22V-S
Heating1Output CapacitykW5.92~14.946.48~16.387.29~18.518.10~20.568.91~22.35
Input Power kW1.15~3.201.29~3.581.39~3.981.56~4.491.73~5.06
COP-4.67~5.124.57~5.014.65~5.254.58~5.204.42~5.13
Input CurrentA2.05~5.712.31~6.412.49~7.122.79~8.033.09~9.06
Heating2Output CapacitykW5.18~14.305.93~16.586.67~18.657.41~20.688.15~21.15
Input Power kW1.33~4.691.39~5.631.58~6.431.77~7.181.97~7.50
COP-3.05~3.892.94~4.262.90~4.222.88~4.182.82~4.13
Input CurrentA2.38~8.392.48~10.072.83~11.503.17~12.843.52~13.42
Heating3Output CapacitykW7.52~16.578.95~19.4210.07~21.8511.18~24.0512.30~25.5
Input Power kW1.37~3.561.62~4.211.84~4.772.08~5.312.33~5.73
COP-4.66~5.474.61~5.524.58~5.464.53~5.384.45~5.28
Input CurrentA2.45~6.372.90~7.533.29~8.533.72~9.504.17~10.25
Cooling4Output CapacitykW6.02~12.317.23~14.828.13~15.729.03~16.679.93~17.50
Input Power kW1.87~4.532.27~5.432.64~5.863.00~6.363.35~6.78
EER-2.73~3.222.73~3.182.68~3.082.62~3.012.58~2.96
Input CurrentA3.34~8.104.06~9.714.72~10.485.37~11.386.00~12.13
Power Supply V/PH/HZ380-415V/3/50Hz
ErP level(35ºC)-A+++A+++A+++A+++A+++
ErP level(55ºC)-A++A++A++A++A++
Water Side Heat Exchanger -Plate heat exchanger
Display controller -LCD touch screen
Backup heater (Optional) kW3kW 
Expansion vessel-5L
Refrigerant Type -R32
Max Water Temperature
(without backup heater)
ºC60
Working Ambeint TemperatureºC-25~43
Water connection inchG1-1/4
Sound pressure Level @1m outdoor unitdB(A)5356565858
indoor unitdB(A)2727272727
Net Dimension (L*W*H) outdoor unitmm1065*410*9601065*410*9601150*430*13501150*430*13501150*430*1350
indoor unitmm475*220*800475*220*800475*220*800475*220*800475*220*800

Note:
1.Outdoor air temperature 7ºC DB,6ºC WB;EWT 30ºC,LWT 35ºC.
2.Outdoor air temperature 7ºC DB,6ºC WB;EWT 47ºC,LWT 55ºC.
3.Outdoor air temperature 20ºC DB,15ºC WB;EWT 15ºC,LWT 55ºC.
4.Outdoor air temperature 35ºC DB,24ºC WB;EWT 12ºC,LWT 7ºC.