60Hz 80kw Yuchai Electricity Power Generating Set

Min.Order: 1
Product origin: Xiamen, Fujian, China
Infringement complaint: complaintComplaint
US$ 6000 ~ 10000

Description
YCW-100T6 powered by: Yuchai YC4D140-D33
Diesel Genset Features                                                                                                                   P.F=0.8  3Phase
Generating Set Performance 60Hz
Service P.R.PStandby
Rated outputkVA100110
Active power outputkW8088
Rated Speedr.p.m1800
Standard VoltageV480/277
Voltage availableV380/220 - 440/254
Prime Mover Performance                                                                                     1800 r.p.m
SERVICEkVAP.R.PStandby
Rated outputKW95104.5
Manufacturer Yuchai
4 stroke Diesel Engine - Injection type Direct
Aspiration type Naturally 
Cylinders, number and arrangement 4-L
Bore×Strokemm 108X115
Total DisplacementL4.21
Cooling system Water
Lube oil specifications SAE 15 W 40
Compression ratio 16.7:1
Specific fuel consumption(P.R.P)L/H25.6
Specific oil consumption(at full load)%<0.1
Total coolant capacity(engine only)L30
Speed governor TypeElectronic
Lube oil system including sump, filters, etc.L13
 


GTL Generator configuration
Engine:   Brand new genuine in warranty
 Alternator:  Brand new brushless alternator, IP23, H insulation class.
Base Frame:Heavy-duty steel channel base frame.
Radiator: With safety guard.
Vibration DamperVibration damper between Engine/Alternator and base frame
Breaker: 3-pole output manual circuit breaker as standard,  4 poles for option
Controller:    Comap AMF9, AMF20, AMF25 for option.DSE702,DSE6020 DSE6120 DSE7320 DSE7420 and other deepsea models, 
Silencer:  Heavy duty industrial type silencer with flexible bellow,elbow.  
Battery:    Varta Brand, high capacity sealed maintenance-free battery c/w battery cables.
Fuel Tank: 8 hours base fuel tank, External Daily Fuel Tank for option
Accessory:Standard tool kits and complete operation/maintenance/manuals for Generator/Engine/Alternator/control panel, etc.
 
Inquiry Items 
Before we talk about diesel generators and make an offer for you, and in order to make a good choice for you, please kindly allow me to ask you the following issues and kindly fill in the blanks:
Genset parameter
Prime power Standby power Voltage FrequencyPhaseQuantityAnother requirement
kvakwkva kwV50Hz or 60hz1 or 3 phaseset
         
 
Voltage&Frequency50hz 380-440/ 190-220/ 220-254
60hz 416-480/ 380-416/ 240-277/ 208-240
 
Requirement of brand
Engine AlternatorControl ModuleATS(Include or not)
    
 
Engine:Cummins, Perkins, FPT, MTU, Volvo, Doosan,Deutz,Yanmar, Kubota, Chinese brand
Alternator:Leroy Somer, Stamford, Marathon, Meccalte, Chinese brand
Controller:Deepsea, Comap, Deif
Circuit Breaker:ABB/SCHNEIDER
 
Physical conditions
Ambient temperatureSea level heightRelative Humidity 
(ºC)(m)(%)
   