Generator power converter | DMGC300K | DMGC500K | DMGC1000K | ||
Generator rated power | 300KW | 500KW | 1000KW | ||
Rated voltage of generator (AC) | 400V/690V | 400V/690V | 400V/690V | ||
Input voltage range (AC) | 0-550V/0-800V | 0-550V/0-800V | 0-550V/0-800V | ||
Rated output power (AC) | 300KW | 500KW | 1000KW | ||
MPPT MPPT Voltage range (AC) | 250-500V/400-750V | 250-500V/400-750V | 250-500V/400-750V | ||
Max. Input current (AC) | 476A/276A | 794A/460A | 1588A/920A | ||
Rated output current (AC) | 433A/251A | 722A/418A | 1444A/837A | ||
THD Current harmonic | <3%(At rated power) | ||||
Power factor | >0.99 | ||||
Max. efficiency | 96% | ||||
Electrical structure | Power frequency transformer | ||||
Allowable grid voltage range (AC) | 220V/380V/440V/480V (Three-phase) ±20% | ||||
Allowable grid frequency range | 50Hz/60Hz±10% | ||||
Automatic operation conditions | AC input and power grid meet the requirements, and the power converter operates automatically | ||||
Restart time after power failure | 2min ( Adjustable) | ||||
General parameters | |||||
Function | Rectification, wind turbine curve setting, adjustable output power | ||||
Automatic protection | Reverse connection protection, short circuit protection, island effect protection, LVRT, overheat protection, overload protection, ground fault protection, lightning arrester, etc | ||||
Display | Touch screen | ||||
Monitoring content | Generator voltage, current, power, inverter output power, * cumulative power generation, * power generation at any time | ||||
Protection level | IP20(Indoor)IP65 (Outdoors) | ||||
Telematics | RS485/USB/GPRS/WIFI/Ethernet (Optional) | ||||
Environment | -10-50°C,<90% Operating amb. Temp. & Hum -10-50°C,<90% no condensation | ||||
Noise (1m) | <70dB | ||||
Refrigeration mode | Forced air cooling | ||||
\ size / weight | 2010*1060*2000mm 1.5t | 2800*1200*2000mm 2.5t | 4000*1200*2000mm 4t |