High Efficiency 400 Litres Split Solar Heat Pump Water Heater
Hot Water Production Volume
Model | AM010B | AM018B | AM023B | AM036B | AM045B | AM070B | AM090B | AM120B | |
Hot Water Output Volume | Liters/hour | 210 | 380 | 490 | 770 | 960 | 1500 | 1900 | 2500 |
Remark: 1) At abient temperature DB20degC, water heated from 15-55degC; 2)Above data is for reference only; |
Reliable and efficient components
Technical Parameters
High Efficiency 400 Litres Split Solar Heat Pump Water Heater | |||||
Model | AM010B | AM018B | AM023B | AM036B | |
Rated Heating Output 1) | kW | 10 | 18 | 23 | 36 |
Coefficient of Performance (COP) 1) | 4.06 | 4.1 | 4 | 4 | |
Rated Input Power 1) | kW | 2.46 | 4.4 | 5.75 | 9 |
Rated Running Current 1) 2) | Amp | 4.4 | 7.8 | 11.5 | 17 |
Max. Running Current | Amp | 7.4 | 14 | 16 | 25 |
Power Supply | 380V/3N~ 50Hz | 380V/3N~ 50Hz | 380V/3N~ 50Hz | 380V/3N~ 50Hz | |
No. of Compressor | unit | 1 | 1 | 1 | 2 |
Brand/Type of Compressor | Scroll | Scroll | Scroll | Scroll | |
Min/Max Operating Outdoor Temperature | °C | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 |
Min/Max. Water Outlet Tempearture | °C | 30 to 60 | 30 to 60 | 30 to 60 | 30 to 60 |
Type of Heat Pump | Air to Water | Air to Water | Air to Water | Air to Water | |
Type of Controller | Wired Controller Panel with Display and Buttons | ||||
Way of Defrost | Reverse Cycle | Reverse Cycle | Reverse Cycle | Reverse Cycle | |
Type of Water Heat Exchanger (Condenser) | Copper, Tube-in-Shell Heat Exchanger | ||||
Type of Air Heat Exchanger (Evaporator) | Hydrophilic Aluminium Fin-Tube Heat Exchanger | ||||
Air Discharge Direction | Vertical | Vertical | Vertical | Vertical | |
No. of Fan Motor | 1 | 1 | 1 | 2 | |
Protection Grade | IPx4 | IPx4 | IPx4 | IPx4 | |
Noise (at distance 1m) | dB(A) | 56 | 56 | 59 | 60 |
Packing Dimension (WxDxH, Plywood) | mm | 860x810x1020 | 880x810x1230 | 930x870x1240 | 1680x780x1230 |
Net Weight | kg | 110 | 130 | 150 | 240 |
REMARKS | 1) At outdoor temperature DB20°C, water circulating heated from 15°C to 55°C; | ||||
2) Water temperature difference between water outlet and water inlet, ΔT=5°C; |
Model | AM045B | AM070B | AM090B | AM120B | |
Rated Heating Output 1) | kW | 45 | 70 | 90 | 120 |
Coefficient of Performance (COP) 1) | 4 | 4 | 4 | 4.3 | |
Rated Input Power 1) | kW | 11.25 | 17.5 | 22 | 27.8 |
Rated Running Current 1) 2) | Amp | 19.5 | 30 | 40 | 53 |
Max. Running Current | Amp | 30 | 45 | 60 | 75 |
Power Supply | 380V/3N~ 50Hz | 380V/3N~ 50Hz | 380V/3N~ 50Hz | 380V/3N~ 50Hz | |
No. of Compressor | unit | 2 | 2 | 2 | 2 |
Brand/Type of Compressor | Scroll | Scroll | Scroll | Scroll | |
Min/Max Operating Outdoor Temperature | °C | -7 to 43 | -7 to 43 | -7 to 43 | -7 to 43 |
Min/Max. Water Outlet Tempearture | °C | 30 to 60 | 30 to 60 | 30 to 60 | 30 to 60 |
Type of Heat Pump | Air to Water | Air to Water | Air to Water | Air to Water | |
Type of Controller | |||||
Way of Defrost | Reverse Cycle | Reverse Cycle | Reverse Cycle | Reverse Cycle | |
Type of Water Heat Exchanger (Condenser) | Copper, Tube-in-Shell Heat Exchanger | ||||
Type of Air Heat Exchanger (Evaporator) | Hydrophilic Aluminium Fin-Tube Heat Exchanger | ||||
Air Discharge Direction | Vertical | Vertical | Vertical | Vertical | |
No. of Fan Motor | 2 | 2 | 2 | 2 | |
Protection Grade | IPx4 | IPx4 | IPx4 | IPx4 | |
Noise (at distance 1m) | dB(A) | 68 | 72 | 72 | 72 |
Packing Dimension (WxDxH, Plywood) | mm | 1740x880x1550 | 2250x1260x2260 | 2250x1260x2260 | 2250x1260x2260 |
Net Weight | kg | 265 | 750 | 750 | 860 |
REMARKS | 1) At outdoor temperature DB20°C, water circulating heated from 15°C to 55°C; | ||||
2) Water temperature difference between water outlet and water inlet, ΔT=5°C; |