Power input | Input Voltage | 380-460V (-15% ~ + 10%), three-phase |
Input Frequency | 45-65Hz | |
Allowable voltage fluctuation | Voltage unbalance <3% | |
Instant-drop | Three-phase AC380-460V power supply, under voltage protection will work in 15ms if the input voltage is lower than AC300V | |
Power output | Voltage | 0 VAC ~ Input voltage |
Overload Class | Stable working in the case of 40 ºC, heavy duty 150%, 1min | |
Efficiency (full load) | ≥0.94 | |
Output frequency accuracy | ± 0.01% (digital command -10 ~ + 45 ºC) ; ± 0.1% (simulation instruction 25 ± 10 ºC) | |
Digital I / O | Opto-isolated input | 7 channels, 24V high active low can be set, input function can be defined |
Open collector | 2 channels, Output functions can be defined | |
Relay output | 2 channels, normally open contacts, contact capacity: inductive, 1.5A / 250VAC, output function defined | |
Analog I / O | Analog Input Voltage | 2 channels, accuracy 0.1%; Voltage:-10V~ + 10VDCOr Current: 0-20mA optional signal |
Analog voltage output | 2 channels, accuracy 0.1%; Voltage:-10V~ + 10VDCOr Current: 0-20mA optional signal | |
Control characteristics | Carrier frequency | 1.1-8 kHz; load characteristics, the carrier frequency can be automatically adjusted |
Frequency setting resolution | 0.01Hz (digital command),± 0.06Hz / 120Hz (11bit + unsigned analog instruction) | |
Run command channel | operation panel, control terminal, communication | |
frequency Setting channel | operation panel, digital/analog input, communication, performance function setting | |
Torque boost | Automatic torque boost; Manual torque boost | |
V/F curve | V/F Curve linear V/F And three curves of torque-derating can be defined | |
Automatic voltage regulation (AVR) | The output PWM can be Automatically adjusted according to the fluctuation of the bus, thereby reducing the influence of voltage fluctuations of the output voltage ripple | |
non-stop operation | in case of instant power failure, uninterrupted operation can be guaranteed by controlling the bus voltage | |
DC braking capacity | Braking current:0.0~120.0% Of rated current | |
Special feature | Parameter copy | Parameter upload and download can be achieved via operating panel with the progress bar |
Process PID | It can be used for closed-loop control of the process | |
Common DC bus | Full power range supports the common DC bus | |
Motor protection | Locked rotor | |
Motor overload | ||
Speed limit | ||
Frequency Drive protection | Output current limit | |
Inverter overload | ||
IGBT I²t overload | ||
Input Supply Undervoltage / Overvoltage | ||
DC bus under-voltage / overvoltage | ||
IGBT overheating | ||
Radiator overheating | ||
electricity failure |