Model | 48 / 3000 HE |
Part number | 241119.105MC |
INPUT DATA | |
Voltage (nominal) | 185 - 275 VAC / 185 - 275 VDC |
Voltage (range) | 85 - 300 VAC / 85 - 300 VDC |
Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz |
Current (maximum) @ nominal input, full load | 19.2 Adc |
Protection | Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC |
OUTPUT DATA | |
Voltage (default) | 53.5 VDC |
Voltage (adjustable range) | 43.5 - 57.6 VDC |
Power (maximum) | 3000 W |
Power @ 85 VAC | 1380 W |
Current (maximum) @ nominal input, full load | 62.5 A |
Ripple, 30MHz bandwidth | < 150 mVpp |
Psophometric noise | < 2 mVRMS |
Static Voltage regulation | ±0.5% for 10 - 100% load |
Dynamic Voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms |
Protection | Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting |
OTHER SPECIFICATIONS | |
Efficiency @ nominal input | 96 % |
Isolation | 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth |
Alarms: Red LED 'on' | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure |
Warnings: Yellow LED 'on' | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage |
Normal (module running): Green LED 'on' | |
Acoustic noise, full load @ Tambient = 25°C full load @ Tambient = 40°C | < 20 dBA < 56 dBA |
MTBF (Telcordia SR-332 Issue I method III (a)) | >350 000 (@ Tambient : 25 °C) |
Operating temperature | -40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing |
Temperature de-rating | >55°C (131°F), 1200W @ 75°C (167°F) |
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (4.25 x 1.69 x 13") / 1.95 kg (4.3 lbs) |
DESIGN STANDARDS | |
Electrical safety | EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013, UL 60950-1:2014, CSA C22.2 No.60950-1-07:2014, IEC 60950-1:2013 |
EMC | EN 61000-6-1:2019, -6-2:2019, - 6-3:2007 + A1:2011, - 6-4:2019, EN 61000-3-2:2019 ETSI EN 300 386 V.2.1.1, Telcordia NEBS GR1089 CORE |
Marine | DNVGL-CG-03392) |
Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |
1 | Rectifier module | Emerson /Vertiv | R48-1800A | |
2 | Rectifier module | Emerson /Vertiv | R48-2000A3 | |
3 | Rectifier module | Emerson /Vertiv | R48-2900U | |
4 | Rectifier module | Emerson /Vertiv | R48-3000e3 | |
5 | Rectifier module | Emerson /Vertiv | R48-3500e | |
6 | Rectifier module | Emerson /Vertiv | R48-5800A | |
7 | Rectifier module | Huawi | R4850N1 | |
8 | Rectifier module | Huawi | R4850G1 | |
9 | Rectifier module | Eltek | Flatpack2 48/2000 HE 241115.105 | |
10 | Rectifier module | Eltek | Flatpack2 48/1000 HE 241122.105 | |
11 | Rectifier module | Eltek | Flatpack2 48/3000 HE 241119.105 | |
12 | Rectifier module | Eaton | APR24-3G |
Wuhan Unique Mechanical And Electrical Equipment Co., LTD. is a high-tech enterprises with a combination of of science, industry and trade. We mainly engaged in R&D and manufacturing of network center room equipment, such as PDU, ODF, CMA, Fiber Spool Frame, Network Panel, Network Cabinet, OF Jointing Box, Fiber Optic Connector, ADSS Cable, Micro Fiber, Pigtail, Patch Cord, UTP Cable, etc. Provide high level of technical consultation and technical services.