A02H series (Air source heat pump water heater circulation type) | ||||||||||||||
HW03Ps-E3 | HW05Ps-E5 | HW03P-E3 | HW05P-E5 | HW07P-E5 | HW10P-C24 | HW14P-C24 | HW20P-C48 | HW24P-C48 | HW30P-C48 | HW36P-C48 | HW48P-C96 | |||
Rated heating capacity | kW | 12 | 19 | 12 | 19 | 25 | 35 | 50 | 75 | 85 | 105 | 125 | 165 | |
Rated input power | kW | 2.75 | 4.39 | 2.75 | 4.37 | 5.75 | 8.10 | 11.57 | 17.20 | 19.60 | 24.20 | 28.90 | 38.10 | |
Rated input current | A | 14.05 | 23.10 | 5.17 | 8.34 | 10.77 | 15.00 | 23.86 | 31.80 | 37.00 | 46.10 | 53.50 | 72.30 | |
Maximum input power | kW | 3.38 | 5.40 | 3.38 | 5.38 | 7.07 | 9.96 | 14.23 | 21.16 | 24.11 | 29.77 | 35.55 | 46.86 | |
Maximum input current | A | 18.28 | 29.19 | 6.43 | 10.21 | 13.44 | 18.93 | 27.05 | 40.20 | 45.81 | 56.56 | 67.54 | 89.04 | |
Performance coefficient(COP) | / | 4.36 | 4.33 | 4.36 | 4.35 | 4.35 | 4.33 | 4.32 | 4.36 | 4.34 | 4.34 | 4.33 | 4.33 | |
Rated hot water output temp. | ºC | 55 | ||||||||||||
Max. hot water output temp. | ºC | 60 | ||||||||||||
Rated hot water produce capacity | L/H | 258 | 408 | 258 | 408 | 537 | 752.5 | 1075 | 1612.5 | 1827.5 | 2257.5 | 2687.5 | 3547.5 | |
Power supply | 1N 220V/50Hz | 3N 380V/50Hz | ||||||||||||
Compressor | Type | Hermetic scroll type | ||||||||||||
Start Mode | Directly start | |||||||||||||
Quantity | Set | 1 | 1 | 1 | 1 | 1 | 2 | 2 | 4 | 2 | 3 | 3 | 4 | |
Water side heat exchanger | Type | Shell & coil(tube) heat exchanger | ||||||||||||
Water flow | m3/h | 2.1 | 3.3 | 2.1 | 3.3 | 4.3 | 6.0 | 8.6 | 12.9 | 14.6 | 18.1 | 21.5 | 28.4 | |
Water Pressure Drop | kPa | ≤50 | ≤55 | ≤50 | ≤55 | ≤55 | <60 | <60 | <65 | <65 | <65 | <65 | <65 | |
Pipe size | DN | DN20 | DN25 | DN20 | DN25 | DN25 | DN32 | DN32 | DN50 | DN50 | DN50 | DN65 | DN80 | |
Protections | 1. High pressure and low pressure protection, 2. Anti-freezing protection, 3. High temperature protection, 4. Too big of the water temperature difference for outlet and inlet protection, 5. Overload protection, 6. Lack phase protection, 7. Reverse phase protection, etc.. | |||||||||||||
Refrigerant | Throttle Type | Electronic expansion valve | ||||||||||||
Quantity | kg | 1.9 | 2.8 | 1.9 | 2.8 | 4.1 | 2.8×2 | 4.1×2 | 3.2×4 | 7.6×2 | 6.2×3 | 7.6×3 | 7.6×4 | |
Noise | DB(A) | ≤55 | ≤63 | ≤55 | ≤63 | ≤65 | ≤65 | ≤68 | ≤70 | ≤72 | ≤73 | ≤74 | ≤78 | |
Dimension | mm | 700×680× 875 | 820×695× 1060 | 700×680× 875 | 820×695× 1060 | 820×695× 1060 | 1000×1000×1858 | 1000×1000×1858 | 1000×2050×1900 | 1000×2050×1900 | 1000×2050×1980 | 1000×2050×1980 | 2000×2050×1980 | |
Net Weight | kg | 100 | 160 | 100 | 160 | 190 | 310 | 400 | 605 | 650 | 835 | 840 | 1230 | |
Testing conditions: | ||||||||||||||
1. Application side initial water temperature: 15ºC, end temperature 55ºC, max. temperature 60ºC. | ||||||||||||||
2. Ambient temperature dry bulb 20ºC, wet bulb 15ºC. | ||||||||||||||
The above parameters are based on Refrigearnt R410a, for parameters based on other refrigerant please contact us. | ||||||||||||||
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product label when buy, or refer to us for any information. Our company keeps the right to interpret. |