Technical indicators | 380V soft starter | 690V soft starter | 1140V soft starter |
Rated working voltage (Ue) | AC380V, +15%, -20% | AC690V, +15%, -20% | ACl140V, +15%, -20% |
Rated working current (Le) | 17A ~ 990A, see type selection comparison table 1 | 17A ~ 990A, see type selection comparison table 2 | 17A ~ 990A, see type selection comparison table 3 |
Adaptive motor power | 7.5kW ~ 500kW, see type selection comparison table 1 | 11kW ~ 500kW, see type selection comparison table 1 | 22kW ~ 500kW, see type selection comparison table 1 |
Meet the standard | GB140486, IEC947-4-2 | ||
Usage category | AC-53b control cage motor, short circuit (bypass) soft starter during operation | ||
Rated frequency | 50Hz or 60Hz (to be stated when ordering) | ||
Rated working system S | 10 operating cycles/hour | ||
Design type | Type 1 | ||
Degree of protection | IP20 | ||
Class of pollution | 3 | ||
Rated control power supply voltage Us | AC220V, + 20%, - 30%, AC110V optional | ||
Control power consumption | ≤5W | ||
Overload protection | Overload protection is divided into four tripping levels: 10A, 10, 20, and 30 (panel adjustable) | ||
communication interface | RS-485 standard interface | ||
Communication rate | 2400bps, 4800bps, 9600bps, 19200bps optional | ||
Communication data format | 8-bit data bit, 1-bit start bit, 1-bit stop bit, no check bit (other formats can be customized) | ||
Communication protocol | MODBUS standard communication protocol | ||
Ambient temperature | For: - 20 ~ + 60 ºC (2% derating for every 1 ºC above 45 ºC), storage: - 40 ~ + 70c | ||
Ambient humidity | ≤ 95% without condensation or dripping | ||
Working height | Altitude ≤ 5km (no capacity reduction within 1KM, 1% reduction for every 100m above 1Km) | ||
Cooling mode | Natural air cooling |
Starter model | Rated current | Adaptive motor power (kW) | Outline specification | Specification of adaptive fast fuse (A) | Optional specification of external current transformer | |
Standard load | Heavy load | |||||
VSG100H017 | 17 | 7.5 | 5.5 | A | 50 | 75A/5A |
VSG100H022 | 22 | 11 | 7.5 | A | 63 | |
VSG100H032 | 32 | 15 | 11 | A | 100 | |
VSG100H038 | 38 | 18.5 | 15 | A | 100 | |
VSG100H047 | 47 | 22 | 18.5 | A | 125 | |
VSG100H062 | 62 | 30 | 22 | A | 200 | 200A/5A |
VSG100H075 | 75 | 37 | 30 | A | 200 | |
VSG100H088 | 88 | 45 | 37 | A | 250 | |
VSG100H110 | 110 | 55 | 45 | A | 315 | |
VSG100H140 | 140 | 75 | 55 | A | 400 | |
VSG100H170 | 170 | 90 | 75 | B | 400 | 500A/5A |
VSG100H210 | 210 | 110 | 90 | B | 700 | |
VSG100H250 | 250 | 132 | 110 | B | 700 | |
VSG100H320 | 320 | 160 | 132 | B | 1000 | |
VSG100H370 | 370 | 185 | 160 | B | 1000 | |
VSG100H410 | 410 | 220 | 185 | B | 1250 | 1000A/5A |
VSG100H480 | 480 | 250 | 220 | B | 1250 | |
VSG100H590 | 590 | 315 | 250 | B | 1800 | |
VSG100H660 | 660 | 355 | 315 | C | 1800 | |
VSG100H790 | 790 | 400 | 355 | C | 2500 | |
VSG100H990 | 990 | 500 | 500 | C | 3000 |
Starter model | Rated current | Adaptive motor power (kW) | Outline specification | Specification of adaptive fast fuse (A) | Optional specification of external current transformer | |
Standard load | Heavy load | |||||
VSG100H017M6 | 17 | 11 | 7.5 | A | 50 | 75A/5A |
VSG100H022M6 | 22 | 15 | 11 | A | 63 | |
VSG100H032M6 | 32 | 22 | 15 | A | 100 | |
VSG100H038M6 | 38 | 30 | 22 | A | 100 | |
VSG100H047M6 | 47 | 37 | 30 | A | 125 | |
VSG100H062M6 | 62 | 45 | 37 | A | 200 | 200A/5A |
VSG100H075M6 | 75 | 55 | 45 | A | 200 | |
VSG100H088M6 | 88 | 75 | 55 | A | 250 | |
VSG100H110M6 | 110 | 90 | 75 | A | 315 | |
VSG100H140M6 | 140 | 110 | 90 | B | 400 | |
VSG100H170M6 | 170 | 132 | 110 | B | 400 | 500A/5A |
VSG100H210M6 | 210 | 160 | 132 | B | 700 | |
VSG100H250M6 | 250 | 220 | 160 | B | 700 | |
VSG100H320M6 | 320 | 250 | 220 | B | 1000 | |
VSG100H370M6 | 370 | 315 | 250 | B | 1000 | |
VSG100H410M6 | 410 | 355 | 315 | B | 1250 | 1000A/5A |
VSG100H480M6 | 480 | 400 | 355 | B | 1250 | |
VSG100H590M6 | 590 | 560 | 400 | C | 1800 | |
VSG100H660M6 | 660 | 630 | 560 | C | 1800 | |
VSG100H790M6 | 790 | 710 | 630 | C | 2500 | |
VSG100H990M6 | 990 | 900 | 710 | C | 3000 |
Starter model | Rated current | Adaptive motor power (kW) | Outline specification | Specification of adaptive fast fuse (A) | Optional specification of external current transformer | |
Standard load | Heavy load | |||||
VSG100H017M11 | 17 | 22 | 15 | A | 50 | 75A/5A |
VSG100H022M11 | 22 | 30 | 22 | A | 63 | |
VSG100H032M11 | 32 | 45 | 30 | A | 100 | |
VSG100H038M11 | 38 | 55 | 45 | A | 100 | |
VSG100H047M11 | 47 | 75 | 55 | A | 125 | |
VSG100H062M11 | 62 | 90 | 75 | A | 200 | 200A/5A |
VSG100H075M11 | 75 | 110 | 90 | A | 200 | |
VSG100H088M11 | 88 | 132 | 110 | A | 250 | |
VSG100H110M11 | 110 | 160 | 132 | B | 315 | |
VSG100H140M11 | 140 | 220 | 160 | B | 400 | |
VSG100H170M11 | 170 | 250 | 220 | B | 400 | 500A/5A |
VSG100H210M11 | 210 | 280 | 250 | C | 700 | |
VSG100H250M11 | 250 | 360 | 280 | C | 700 | |
VSG100H320M11 | 320 | 420 | 360 | C | 1000 | |
VSG100H370M11 | 370 | 570 | 420 | C | 1000 | |
VSG100H410M11 | 410 | 630 | 570 | C | 1250 | 1000A/5A |
VSG100H480M11 | 480 | 720 | 630 | C | 1250 | |
VSG100H590M11 | 590 | 880 | 720 | C | 1800 | |
VSG100H660M11 | 660 | 1000 | 880 | C | 1800 | |
VSG100H790M11 | 790 | 1200 | 1000 | C | 2500 | |
VSG100H990M11 | 990 | 1500 | 1200 | C | 3000 |
Application machine type | Current limiting starting | Voltage ramp start | ||||
Current limiting multiple A | Timeout b (s) | Soft stop time d (s) | Initial voltage U | Starting time B (s) | Soft stop time d (s) | |
centrifugal pump | 3.0 | 20 | 5 | 20 | 5 | 5 |
Piston compressor | 3.5 | 25 | 0 | 20 | 5 | 0 |
Centrifugal compressor | 3.5 | 25 | 0 | 20 | 10 | 0 |
Screw compressor | 3.0 | 30 | 0 | 20 | 5 | 0 |
Induced draft fan | 3.0 | 50 | 0 | 25 | 40 | 0 |
Blower | 3.0 | 50 | 0 | 25 | 40 | 0 |
Lifting machinery | 3.5 | 25 | 0 | 20 | 5 | 0 |
blender | 3.5 | 25 | 0 | 25 | 5 | 0 |
Crusher | 4.0 | 20 | 0 | 25 | 10 | 0 |
Conveyor belt | 3.5 | 30 | 0 | 20 | 5 | 0 |
Grinding machine | 4.0 | 20 | 0 | 25 | 5 | 0 |
press | 4.0 | 20 | 0 | 25 | 20 | 0 |
Escalator | 3.0 | 20 | 0 | 20 | 5 | 0 |