Serial number | Type | Description |
1 | 60227 IEC 01(BV) | Single core rigid conductor unsheathed cable |
2 | 60227 IEC 02(RV) | Single core flexible conductor unsheathed cable |
3 | 60227 IEC 05(BV) | Single core 70ºC solid conductor unsheathed cable |
4 | 60227 IEC 06(RV) | Single core 70ºC flexible conductor unsheathed cable |
5 | 60227 IEC 07(BV-90) | Single core 90ºC solid conductor unsheathed cable |
6 | 60227 IEC 08(RV-90) | Single core 90ºC flexible conductor unsheathed cable |
7 | 60227 IEC 10(BVV) | Light PVC sheathed cable(NYY or NYM) |
8 | 60227 IEC 42(RVB) | Flat unsheathed flexible wire |
9 | 60227 IEC 52(RVV) | Light PVC sheathed flexible wire |
10 | 60227 IEC 53(RVV) | Common PVC sheathed flexible wire |
11 | BV | Copper conductor PVC insulated wire(H07V-U or H07V-R) |
12 | BLV | Aluminum conductor PVC insulated wire |
13 | BVR | Copper conductor PVC insulated flexible cable(H07V-R) |
14 | BVV | Copper conductor PVC insulated sheathed |
15 | BLVV | Aluminum conductor PVC insulated and sheathed round cable |
16 | BVVB | Copper conductor PVC insulated and sheathed flat cable |
17 | BLVVB | Aluminum conductor PVC insulated sheathed flat cable |
18 | NMD | Copper conductor PVC/Nylon Insulated PVC Jacked flat cable |
19 | RVS | Twisted copper conductor PVC insulated flexible cable for conection |
20 | AVP | Copper conductor PVC insulated wire with shield for installation |
21 | RVP | Copper conductor PVC insulated flexible wire with shield |
22 | RVVP | Copper conductor PVC insulated, shielded, |
CONDUCTOR | INSULATION | MAX.COND RESISTANCE (Ω/KM) | UNIT LENGTH (M)(FT) | |||
SIZE (AWG) | CONSTRUCTION (NO./mm) | DIAMETER (mm) | NOMINAL THICKNESS (mm) | DIAMETER (mm) | ||
30 | 7/0.10 | 0.3 | 0.8 | 1.9 | 381 | 610(2000) |
28 | 1/0.32 | 0.32 | 0.79 | 1.9 | 227 | |
7/0.127 | 0.38 | 0.81 | 2 | 239 | ||
26 | 1/0.404 | 0.4 | 0.8 | 2 | 143 | |
7/0.16 | 0.48 | 0.81 | 2.1 | 150 | ||
24 | 1/0.511 | 0.51 | 0.8 | 2.1 | 89.3 | |
11/0.16 | 0.61 | 0.82 | 2.25 | 94.2 | ||
22 | 1/0.643 | 0.64 | 0.8 | 2.25 | 56.4 | |
17/0.16 | 0.76 | 0.82 | 2.4 | 59.4 | ||
20 | 1/0.813 | 0.81 | 0.8 | 2.4 | 35.2 | |
26/0.16 | 0.94 | 0.81 | 2.55 | 36.7 | ||
18 | 1/1.024 | 1.02 | 0.82 | 2.65 | 22.2 | |
41/0.16 | 1.18 | 0.81 | 2.8 | 23.2 | ||
16 | 1/1.29 | 1.29 | 0.81 | 2.9 | 14 | |
26/0.254 | 1.49 | 0.81 | 3.1 | 14.6 | ||
14 | 1/1.60 | 1.6 | 0.8 | 3.2 | 8.78 | |
41/0.254 | 1.88 | 0.81 | 3.5 | 8.96 | ||
12 | 65/0.254 | 2.36 | 0.82 | 4 | 5.64 | |
10 | 105/0.254 | 3.4 | 0.83 | 5.05 | 3.54 |
PVC insulated cable(wire)
Reference Standard:
The product is manufactured according to the standards of GB/T5023-2008 and JB/T8734-2016 or I EC, BS, DIN, and I CEA up on repuest.
Applications:
The product is suitable for power intallation, fixed wiring or flexible connection for electrical appliances with rated voltage of 450/750V and below.
Operating characteristics:
•Rated voltage Uo/U: 450/750V, 300/500V and 300/300V.
•Max. permissible continuous operating temperature of the conductor.
60227 IEC 07 (BV-90) 90°C
60227 IEC 08 (RV-90) 90°C
60227 IEC 56 (RVV-90) 90°C
60227 IEC 57 (RVV-90) 90°C
For other types 70°C
•The ambient temperature under installation shall not be below 0°Co
•The bending radius of cable:
D≤25mm ≥4D
D>25mm ≥6D
(D-Diameter of the cable)