Adl3000-E Multi-Function Three Phase Electrical Energy Meter Smart with Supporting Infrared Communication

Min.Order: 1
Product origin: Shanghai, China
Infringement complaint: complaintComplaint
US$ 70

Description
1.Overview
ADL3000 is a smart meter designed for power supply system, industrial and mining enterprises and utilities to calculate the electricity consumption and manage the electric demand. It features the high precision, small size and simple installation. It integrates the measurement of all electrical parameters with the comprehensive electricity metering and management provides various data on previous 12 months, checks the 31st harmonic content and the total harmonic content, realizes the remote communication and the remote control with switching input and relay output and boasts the alarm output. It is fitted with RS485 communication port and adapted to MODBUS-RTU. DTSD1352 can be used in all kinds of control systems, SCADA systems and energy management systems. All meters meet the related technical requirements of electronic power meter in the IEC62053-21,IEC62053-22 standards.
 
2.Function
Function
Function description
Function provide
Measurement of kWh
Active kWh (positive and negative)
*
Reactive kWh (positive and negative)
*
A, B, C phase positive active kWh
*
Measurement of electrical parameters
U,IP,Q,S,PF,F
*
Measurement of
2~31ST Voltage and current harmonic
Note 1
LCD Display
8 bits section LCD display, background light
*
Key programming
4 keys to communication and set parameters
*
Pulse output
Active pulse output
*
Reactive pulse output
Note 2
Clock pulse output
Note 2
LED alarm
Alarm on voltage loss and overvoltage
*
Multi-tariff and functions
Active switch input
Note 3
Switch output
Note 2
Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates
*
Max demanded kWh and time happened
*
Frozen data on last 48 months, last 90days
*
Date, time
*
Communication
The first communication path: Communication interface: RS485, Communication protocol: MODBUS-RTU and DL/T645-07
*
The second communication path: Communication interface: RS485,Communication protocol: MODBUS-RTU and DL/T645-07
Note 3
Temperature measurement
Support 3 outlay NTC temperature
Note 4
Note: 
1: Harmonic is a standard while choosing outlay transformer, optional for other situation. 
2: Reactive pulse output, clock pulse output and switching output: Choose one of these three. 
3: Active switching, the second communication path: Choose one of these two. 
4: Both 1 and 2 cannot be chosen while choosing temperature measurement.
 
3.Products parameters
Specification
3 phase 3 wires, 3 phase 4 wires
Voltage
Reference voltage
3×100V, 3×380V,3×57.7/100V, 3×220/380V
Consumption
<10VA(Single phase)
Impedance
>2M
Accuracy class
Error±0.2%
Current
Input current
3×1(6)A,3×1(6)A (Outlay transformer),3×10(80)A
Consumption
<1VA(Single phase rated current)
Accuracy class
Error±0.2%
Power
Active, reactive, apparent power, error±0.5℅
Frequency
45~65Hz
Temperature
-40ºC~99ºC
Energy
Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2)
Clock
≤0.5s/d
Energy pulse output
1 active optocoupler output, 1 reactive optocoupler output
Switching output
1 Switching output
Switching input
1 optocoupler input
Width of pulse
80±20ms
Pulse constant
6400imp/kWh,400imp/kWh (Correspond with the basic current)
Interface and communication
RS485:Modbus RTU/DL/T645-0
Range of communication address
Modbus RTU:1~ 247;
Baud rate
1200bps~19200bps
Relative temperature
-25ºC~+55ºC
Relative humidity
≤95℅(No condensation)
 

Package&Delivery       