Specifications | VAPG04-50DF | VAPG04-75DF | VAPG04-100DF | VAPG04-150DF | VAPG04-200DF | VAPG04-300DF | VAPG04-400DF | VAPG04-500DF | VAPG04-600DF | VAPG04-800DF | VAPG04-1000DF | VAPG04-1200DF | |
Rated voltage (VAC) | 400 | ||||||||||||
Input voltage range (VAC) | 400 ± 20% | ||||||||||||
Operating frequency (Hz) | 50±5% | ||||||||||||
Rated capacity (Kvar) | 50 | 75 | 100 | 150 | 200 | 300 | 400 | 500 | 600 | 600 | 800 | 1200 | |
Overload current multiple | 1.2 | ||||||||||||
Overall dimension / M (WxDxH) | 600×800×2200 | 600×800×2200 | 600×800×2200 | 800×800×2200 | 800×800×2200 | 1000×800×2200 | 1400×800×2200 | 1600×800×2200 | |||||
Wire system | Three-phase three lines / three-phase four lines | ||||||||||||
Primary incoming line mode | Lower incoming line / upper incoming line/cabinet busbar | ||||||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | ||||||||||||
Operating ambient humidity (%) | < 95% no condensation | ||||||||||||
Cooling mode | Forced air cooling | ||||||||||||
Degree of protection | IP21/IP20 | ||||||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | ||||||||||||
Number of harmonics that can be filtered | 2 ~ 50 times | ||||||||||||
Harmonic compensation rate | > 95% | ||||||||||||
Response time | ≤10ms | ||||||||||||
Display | TFT true color touch screen, real-time voltage, and current data display | ||||||||||||
Intelligent communication | TCP/IP GPRS Modbus | ||||||||||||
Storage, transportation, temperature | -40 ~ 70 ° C | ||||||||||||
Reliability and life | Design life 20 years | ||||||||||||
electromagnetic compatibility | Comply with GB 7251-2005 (GB 7261-2000) |
Specifications | VAPG06-50DF | VAPG06-100DF | VAPG06-200DF | VAPG06-300DF | VAPG06-400DF | VAPG06-500DF | VAPG06-600DF | VAPG06-800DF | VAPG06-1000DF | VAPG06-1200DF | VAPG06-1600DF | VAPG06-2000DF | ||
Rated voltage (VAC) | 600 | |||||||||||||
Input voltage range (VAC) | 600 ± 20% | |||||||||||||
Operating frequency (Hz) | 50 ± 5% | |||||||||||||
Rated Current (A) | 50 | 100 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1200 | 1600 | 2000 | ||
Overload current multiple | 1.2 | |||||||||||||
Overall dimension / M (WxDxH) | 600×800×2200 | 800×800×2200 | 800×800×2200 | 1000×800×2200 | 1400×800×2200 | 1600×800×2200 | 2000×800×2200 | 2600×800×2200 | ||||||
Wire system | Three-phase three lines | |||||||||||||
Primary incoming line mode | Lower incoming line | |||||||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | |||||||||||||
Operating ambient humidity (%) | < 95% no condensation | |||||||||||||
Cooling mode | Forced air cooling | |||||||||||||
Degree of protection | IP21/IP20 | |||||||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | |||||||||||||
Number of harmonics that can be filtered | 2 ~ 50 times | |||||||||||||
Harmonic compensation rate | > 95% | |||||||||||||
Response time | ≤10ms | |||||||||||||
Display | TFT true color touch screen, real-time voltage, and current data display | |||||||||||||
Intelligent communication | TCP/IP GPRS Modbus | |||||||||||||
Storage, transportation, temperature | -40 ~ 70 ° C | |||||||||||||
Reliability and life | Design life 20 years | |||||||||||||
electromagnetic compatibility | Comply with GB 7251-2005 (GB 7261-2000) |
Specifications | VPVG02-140DF | VPVG02-280DF | VPVG02-420DF | VPVG02-560DF | VPVG02-840DF | VPVG02-1120DF | VPVG02-1400DF | VPVG02-2100DF | VPVG02-2800DF |
Rated voltage (VAC) | 220 | ||||||||
Input voltage range (VAC) | 220±20% | ||||||||
Operating frequency (Hz) | 50±5% | ||||||||
Rated capacity (Kvar) | ±140 | ±280 | ±420 | ±560 | ±840 | ±1120 | ±1400 | ±2100 | ±2800 |
Equivalent capacitance (Kvar) | 210 | 420 | 630 | 840 | 1260 | 1680 | 2100 | 3150 | 4200 |
Rated current (A) | 367 | 735 | 1102 | 1470 | 2204 | 2940 | 3670 | 5512 | 7350 |
Overload current multiple | 1.2 | ||||||||
Overall dimension / M (WxDxH) | 600×800×2200 | 900×800×2200 | 1200×800×2200 | 1800×800×2200 | 2900×800×2200 | 3500×800×2200 | 5000×800×2200 | 6500×800×2200 | |
Wire system | Three-phase three-wire | ||||||||
Secondary incoming line mode | Lower incoming line | ||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | ||||||||
Operating ambient humidity (%) | < 95% no condensation | ||||||||
Cooling mode | Forced air cooling | ||||||||
Degree of protection | IP21/IP20 | ||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | ||||||||
Reactive power regulation range | Continuously adjustable from rated capacitive reactive power to rated inductive reactive power | ||||||||
harmonic | Meet the requirements of power quality and harmonics in the public power grid (GB/T 14549-93) | ||||||||
response time | ≤3ms | ||||||||
display | TFT true color touch screen, real-time voltage, and current data display | ||||||||
Intelligent communication | TCP/IP GPRS Modbus | ||||||||
Storage, transportation, temperature | -40~70ºCC | ||||||||
Reliability and life | Design life 20 years | ||||||||
electromagnetic compatibility | Comply with GB 7251-2005 (GB/T 7261-2000) |
Specifications | VPVG04-50DF | VPVG04-75DF | VPVG04-100DF | VPVG04-150DF | VPVG04-200DF | VPVG04-300DF | VPVG04-400DF | VPVG04-500DF | VPVG04-600DF | VPVG04-800DF | VPVG04-1000DF | VPVG04-1200DF | |
Rated voltage (VAC) | 400 | ||||||||||||
Input voltage range (VAC) | 400±20% | ||||||||||||
Operating frequency (Hz) | 50±5% | ||||||||||||
Rated capacity (Kvar) | ±50 | ±75 | ±100 | ±150 | ±200 | ±300 | ±400 | ±500 | ±600 | ±800 | ±1000 | ±1200 | |
Equivalent capacitance (Kvar) | 75 | 115 | 150 | 225 | 300 | 450 | 600 | 750 | 900 | 1200 | 1500 | 1800 | |
Rated current (A) | 72 | 108 | 144 | 216 | 288 | 432 | 576 | 720 | 864 | 1152 | 1440 | 1728 | |
Overload current multiple | 1.2 | ||||||||||||
Overall dimension / M (WxDxH) | 600×800×2200 | 600×800×2200 | 800×800×2200 | 1000×800×2200 | 1400×800×2200 | 1600×800×2200 | |||||||
Wire system | Three-phase three-wire / three-phase four-wire | ||||||||||||
Secondary incoming line mode | Lower incoming line / upper incoming line/cabinet busbar | ||||||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | ||||||||||||
Operating ambient humidity (%) | < 95% no condensation | ||||||||||||
Cooling mode | Forced air cooling | ||||||||||||
Degree of protection | IP21/IP20 | ||||||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | ||||||||||||
Reactive power regulation range | Continuously adjustable from rated capacitive reactive power to rated inductive reactive power | ||||||||||||
harmonic | Meet the requirements of power quality and harmonics in the public power grid (GB /T 14549-93) | ||||||||||||
response time | ≤3ms | ||||||||||||
display | TFT true color touch screen, real-time voltage, and current data display | ||||||||||||
Intelligent communication | TCP/IP GPRS Modbus | ||||||||||||
Storage, transportation, temperature | -40~70ºCC | ||||||||||||
Reliability and life | Design life 20 years | ||||||||||||
electromagnetic compatibility | Comply with CB 7251-2005 (GB/T 7261-2000) |
Specifications | VPVG06-200DF | VPVG06-300DF | VPVG06-600DF | VPVG06-900DF | VPVG06-1200DF | VPVG06-1800DF | VPVG06-3000DF | VPVG06-6000DF | VPVG06-9000DF |
Rated voltage (VAC) | 600 | ||||||||
Input voltage range (VAC) | 600±20% | ||||||||
Operating frequency (Hz) | 50±5% | ||||||||
Rated capacity (Kvar) | ±200 | ±300 | ±600 | ±900 | ±1200 | ±1800 | ±3000 | ±6000 | ±9000 |
Equivalent capacitance (Kvar) | 300 | 450 | 900 | 1350 | 1800 | 2700 | 4500 | 9000 | 13500 |
Rated current (A) | 192 | 289 | 577 | 866 | 1155 | 1732 | 2887 | 5774 | 8661 |
Overload current multiple | 1.2 | ||||||||
Overall dimension / M (WxDxH) | 600×800×2200 | 600×800×2200 | 900×800×2200 | 1200×800×2200 | 1800×800×2200 | 3500×800×2200 | 6500×800×2200 | 9500×800×2200 | |
Wire system | Three-phase three-wire | ||||||||
Secondary incoming line mode | Lower incoming line | ||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | ||||||||
Operating ambient humidity (%) | < 95% no condensation | ||||||||
Cooling mode | Forced air cooling | ||||||||
Degree of protection | IP21/IP20 | ||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | ||||||||
Reactive power regulation range | Continuously adjustable from rated capacitive reactive power to rated inductive reactive power | ||||||||
harmonic | Meet the requirements of power quality and harmonics in the public power grid (GB/T 14549-93) | ||||||||
response time | ≤3ms | ||||||||
display | TFT true color touch screen, real-time voltage, and current data display | ||||||||
Intelligent communication | TCP/IP GPRS Modbus | ||||||||
Storage, transportation, temperature | -40~70ºCC | ||||||||
Reliability and life | Design life 20 years | ||||||||
electromagnetic compatibility | Comply with GB 7251-2005 (GB 7261-2000) |
Specifications | VPVG1-500DF | VPVG1-1000DF | VPVG1-2000DF | VPVG1-3000DF | VPVG1-4000DF | VPVG1-5000DF | VPVG1-6000DF | VPVG1-8000DF | VPVG1-10000DF | |
Rated voltage (VAC) | 1140 | |||||||||
Input voltage range (VAC) | 1140±20% | |||||||||
Operating frequency (Hz) | 50±5% | |||||||||
Rated capacity (Kvar) | ±500 | ±1000 | ±2000 | ±3000 | ±4000 | ±5000 | ±6000 | ±8000 | ±10000 | |
Equivalent capacitance (Kvar) | 750 | 1500 | 3000 | 4500 | 6000 | 7500 | 9000 | 12000 | 10500 | |
Rated current (A) | 253 | 506 | 1013 | 1520 | 2026 | 2532 | 3039 | 4052 | 5065 | |
Overload current multiple | 1.2 | |||||||||
Overall dimension / M (WxDxH) | 900×900×2200 | 1200×900×2200 | 2400×900×2200 | 3600×900×2200 | 4800×900×2200 | 6000×900×2200 | 7200×900×2200 | 9600×900×2200 | 12000×2200 | |
Wire system | Three-phase three-wire | |||||||||
Secondary incoming line mode | Lower incoming line | |||||||||
Operating ambient temperature (ºC) | -25 ~ + 45 ºC (derating is required above 40 ºC) | |||||||||
Operating ambient humidity (%) | < 95% no condensation | |||||||||
Cooling mode | Forced air cooling | |||||||||
Degree of protection | IP21/IP20 | |||||||||
Working altitude | 0 ~ 3000m (> 2000m, need to reduce capacity) | |||||||||
Reactive power regulation range | Continuously adjustable from rated capacitive reactive power to rated inductive reactive power | |||||||||
harmonic | Meet the requirements of power quality and harmonics in the public power grid (GB/T 14549-93) | |||||||||
response time | ≤3ms | |||||||||
display | TFT true color touch screen, real-time voltage, and current data display | |||||||||
Intelligent communication | TCP/IP GPRS Modbus | |||||||||
Storage, transportation, temperature | -40~70ºCC | |||||||||
Reliability and life | Design life 20 years | |||||||||
electromagnetic compatibility | Comply with GB 7251-2005 (GB 7261-2000) |