Content | Parameters | Remarks | |
Input | Rated input voltage | 3-phase 6 / 10KV (- 35% ~ + 10%) | |
Rated input frequency | 50HZ±3% | ||
Fluctuating voltage | The grid voltage drops within 35%, and the frequency converter operates with derating | ||
power factor | ≥ 0.96 (load greater than 20%) | ||
Output | Rated output voltage | 3-phase 6 / 6.6/10/11kv | |
Rated output current | 100A~1160A | ||
Output power range | 1000≈20000KVA | ||
Basic performance | Overload capacity | 150% 1min 180% immediate protection | The protection curve can be set |
Power system efficiency | 97% | ||
frequency resolution | 0.01Hz | ||
Total harmonic distortion (THD) | Less than 3% | Meet the national standard gb14549-93 and eee519-1992 power quality standards | |
Control interface | display | The multi-language color man-machine interface can simultaneously display basic electrical parameters such as input and output voltage, current and power, as well as real-time operation status, alarm recording, and event recording functions | |
set up | Multi-function parameter setting | ||
operation | Local, remote control, and host computer communication | ||
Control | Analog input / output | 3-channel analog input, 4-channel analog star output voltage type, or current type can be set, and the input and output function can be set to 0 (4) ~ 20mA, 0 (2) ~ 10V, etc. ( 7 types can be selected ) | |
Digital input / output | 38 digital input functions such as 8-channel digital input and 5-channel digital output (expandable internal virtual REV/FWD) can be set, alarm barrier can be set, and 52 digital output functions can be set | ||
Communication function | RS485, MODBUS-RTU (standard), PROFIBUS-DP (optional), TCP / P (optional) | ||
Control power capacity | Single-phase 220 V AC / 3KVA, 50 / 60Hz (DC power supply can be selected according to project needs) | ||
Main control functions | Anti "power shaking" function, unit bypass, system self-diagnosis, automatic current limiting function, etc | ||
Protection function | Overcurrent, overload, short circuit, three-phase current imbalance, instantaneous power failure, input and output phase loss, overvoltage, under-voltage, overheating, external fault interlocking shutdown, unit automatic bypass, and reverse power protection | ||
Environment and others | Ambient temperature/humidity | 10 ~ 45 ºC, 20% ~ 90% (no condensation) | Special environment, please call for consultation |
Altitude | < 1000m | ||
Cooling mode | forced air cooling | ||
Degree of protection | Standard | P30 (anti-salt fog strengthening) container | P45 | ||
Place of use | Indoor, no explosive or corrosive gas, no conductive dust |
Model Number | Rated Capacity | Rated current | Size (mm) and weight (kg) | |||||
L1 | L2 | L3 | W | H | Weight | |||
VSPS-100-066-1000 | 1000 | 100 | 1210 | 1800 | 2420 | 1500 | 2204 | 7000 |
VSPS-100-066-2000 | 2000 | 200 | 1210 | 2300 | 2985 | 1500 | 2304 | 8000 |
VSPS-100-066-3000 | 3000 | 300 | 1210 | 2300 | 2985 | 1500 | 2304 | 8000 |
VSPS-100-066-4000 | 4000 | 400 | 1210 | 2600 | 3428 | 1500 | 2500 | 11000 |
VSPS-100-066-5000 | 5000 | 500 | 1210 | 2600 | 3428 | 1500 | 2500 | 11000 |
VSPS-100-066-6000 | 6000 | 600 | 1210 | 2800 | 3540 | 1800 | 2500 | 13500 |
Model Number | Rated Capacity | Rated current | Size (mm) and weight (kg) | |||||
L1 | L2 | L3 | W | H | Weight | |||
VSPS-100-066-1000 | 1000 | 100 | 1210 | 1800 | 2170 | 1500 | 2204 | 7000 |
VSPS-100-066-2000 | 2000 | 200 | 1210 | 2300 | 2635 | 1500 | 2304 | 8000 |
VSPS-100-066-3000 | 3000 | 300 | 1210 | 2300 | 2635 | 1500 | 2304 | 8000 |
VSPS-100-066-4000 | 4000 | 400 | 1210 | 2600 | 3028 | 1500 | 2500 | 11000 |
VSPS-100-066-5000 | 5000 | 500 | 2410 | 2600 | 3028 | 1500 | 2500 | 11000 |
VSPS-100-066-6000 | 6000 | 600 | 2410 | 2800 | 3140 | 1800 | 2500 | 13500 |