Item | SP5-10 | SP5-20 | SP5-40 | SP5-60 | SP5-80 |
Nominal discharge current In(8/20us) | 5KA | 10KA | 20KA | 30KA | 40KA |
Max discharge current In(8/20us) | 10KA | 20KA | 40KA | 60KA | 80KA |
Max. continuous operating voltage Uc (V) | 270 | 320 | 385 | 420 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 | 270 | 320 | 385 | 460 |
Varistor voltage U1mA (V) | 430 | 510 | 620 | 680 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 | 430 | 510 | 620 | 710 |
Protection level Up (kA) | 1.0 | 1.2 | 1.2 | 1.2 | 1.0 | 1.4 | 1.6 | 1.8 | 1.2 | 1.6 | 1.8 | 2.0 | 1.5 | 1.8 | 2.0 | 2.2 | 1.6 | 1.8 | 2.2 | 2.3 |
Poles | 1P, 2P, 1P+N, 3P, 4P, 3P+N |
Rated working voltage Un(V) | 230/400 |
Response time (ms) | ≤25 |
Test classification | Class II |
IP protection class | IP20 |
Flame class | V0 |
Case material | PBT/PA66 |
Recommended fuse or circuit breaker (A) | 40∽60 |
Installation method | 35mm DIN rail mounting |
Standards | GB/T 18802.11 IEC61643-11 |