3ka, 4.5ka, 6ka Micro 10 AMP Mini Circuit Breaker with CB

Min.Order: 5,000
Product origin: Shanghai, China
Infringement complaint: complaintComplaint
US$ 0.6 ~ 0.65

Description
Introduction
 DAB6-63  are intended for protecting distribution and group systems having different loads:
- electric appliances, lighting - V characteristic switches;
- drives with moderate starting currents (compressor, fan group) - C characteristic switches;
- drives with high starting currents (hoisting mechanisms, pumps) - D characteristic switches;
Miniature circuit breaker DAB6-63 are recommended for use in electrical distribution panels of residential and public buildings.


Advantages
 
  • Two types of short circuit protection.
  • Wide range of operating temperatures from -40 to +50° С.
  • Updated wider engagement lever with improved contact area.
  • Notches on terminal clamps provide for lowering thermal losses and boosting the mechanical stability of connection.


Technical Features
 
MCB DAB6-63
For protection of general power distribution (IEC/EN 60898-1)    
Poles1P2P3P4P
Electrical performance
Functionsshort circuit protection,overload protection,isolationg,control
Rated frequency  f   Hz50-60Hz
Rated working voltage  Ue   V AC230/400400
Rated current  In A6,10,16,20,25,32,40,50,63
Rated insulated voltage Ui  V500
Impulse withstand voltage Uimp   kV4
Instantaneous tripping typeDAB6-63NB/C/D
DAB6-63HB/C/D
Rated short circuit Icn(kA)      DAB6-63N4.5
DAB6-63H6
Release typeThermal magnetic type
Service life(O~C)Mechanical  Actual value20000
 Standard value 4000
Electrical  Actual value8000
 Standard value 4000
Connection and installation
Protection degreeIP20
Wire                                            mm²1~35
Working temperature-5 ~+40ºC
Resistance to humidity and heatClass 2
Altitude above sea2000
Relative humidity+20ºC , 90% ;+40ºC , 50%
Pollution degree2
Installation environmentAvoid obvious shock and vibration
Installation classClass II, Class III
MountingDIN35 rail
Combination with accessories
Auxiliary contactYes
Alarm contactYes
Shunt releaseYes
Undervoltage releaseYes
Auxiliary contact+Alarm contactYes
Dimensions(mm)                                           (WxHxL)                                                                                a17.53552.570
b80.280.280.280.2
c76.576.576.576.5
















Product Tag:
Related categories:
Scroll to Top