220V Single Phase High Frequency Online UPS for Network and Computer

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 1 ~ 100

Description

220V single phase High Frequency Online UPS for Network and Computer

Product Advantages:
1: Cold start
2: Can be with 100% unbalance load
3: Selectable output voltage via LCD
4: Advanced battery management(ABM)
5: Suitable for all kinds of loads, and a high overload capacity
6: Latest soft switch tech in the boost PFC, enable to reduce the PFC IGBT's Voltage spike and switch loss, and improve the UPS capability to resist lighting and Instantaneous over-voltage.


Main Features
1>Double conversion online technology.
2>Sealed lead acid, maintenance free battery.
3>Equipped with maintenance bypass switch.
4>SNMP,RS485 and EMD environmen monitoring.
5>DSP Technology, compact design, cost-save price.
6>Fully meet saltus of the load from 0 to 100%
7>Sufficient Expansion Slots for USB,AS400,CMC monitoring,
8>Support sensitive loads like Air Conditioner, Laser Printer etc.
9>Nice interface design, LCD display the UPS operating status.
10>Latest Tri-level inverter control tech, whole UPS high efficiency ≥94%.
11>True online double conversion technology with microprocessor & DSP control


 

Queen Star Plus Series 6K - 10K Technical Specification
IndexQ6K PlusQ6KL PlusQ10K PlusQ10KL PlusComments
Input
Input voltage
Rated voltage220VAC 
PhaseSingle phase with ground 
Turn on
voltage range
(120±5~274±5)VAC 
Bypass
voltage range
(60±5~300±5)VACCould be adjusted
by software.
Bypass low
loss
60VAC~220VAC(default 60VAC)
Bypass low
comeback
Low loss +5VAC
Bypass high
loss
220VAC~300VAC(default 300VAC)
Bypass high
comeback
High loss -5VAC
Line low loss
/comeback
(120±5) VAC /(140±5) VACload≤50%
(150±5) VAC /(165±5) VAC50%
(160±5) VAC /(175±5) VAC80%
Line high
loss/comeback
(274±5)VAC/(260±5)VAC 
Input frequency
Rated frequency50Hz 
Frequency low loss(40~49) ±0.2Hz(default:46Hz)Could be adjusted
by software.
Frequency low
comeback
Frequency low loss +0.5Hz
Frequency high
loss
(51~60)±0.2Hz(default:54Hz)
Frequency high
comeback
Frequency high loss -0.5Hz
Input power factor
It power
factornpu
> 0.99Q6K Plus & Q6KL Plus:
220VAC, full R load
Q10K Plus & Q10KL Plus:
full R load
GeneratorSupport generator inputGenerator rating
≥2*UPS rating
Input current
Rated current25A27A41A43A 
Input THDI10% 
Output protection
Rating protection32A Breaker50A Breaker 
Output power 
VA/watt6000/480010000/8000 
Rated voltage220VACSine wave
Voltage range200/208/220/230/240VACQ6K Plus & Q6KL Plus:
Could be adjusted by
software. 10% derating
for 208VAC/200VAC.
Voltage regulation±1% 
Voltage distortion≤6%Full RCD load
≤2%Full R load
DC offset≤200mV 
Transient response≤9%R load 0%~100%~0%
≤6%R load
20%~100%~20%
Transient recovery≤60ms voltage recovery to 90%Full RCD load
Bypass output
before turn-on
YES 
Crest ration3:1 
Output frequency range
Normal mode1,Same as input frequency(46Hz~54Hz)
2,50Hz(Input frequency>54Hz or Input frequency<46Hz)
 
Battery mode(50+0.1) Hz 
Slew rate1 Hz/Sec 
Efficiency
Normal mode> 93% 
Battery mode> 91% 
Overload
Normal mode/
battery mode
Overload warning only105%±5%≤load
1min,then transfer to bypass and alarm.105%±5%<load≤
125%±5%
30S,then transfer to bypass and alarm.125%±5%<load≤
135%±5%
100mS, then transfer to bypass and alarm.load>135%±5%
Automatically
retransfer
YES 
Short protection
Normal/
battery mode
YES 
Transfer time
Normal to
battery mode
0mS0mS 
Battery to
normal mode
0mS0mS 
Normal to
bypass mode
<4mS0mSQ6K Plus & Q6KL Plus:
0mS (option)with load
Bypass to
normal mode
<4mS0mS
Battery and charger
Battery
Rated voltage192VDC 
Type/RatingSunshine 7AH/12V Sunshine 9AH/12V  
Battery quantity16 PCS 16 PCS  
Backup time> 14min >8min Half load
Protection
Low alarm voltage/
comeback voltage
(180.8V±4V)/ (188.8V±4V) 
Shutdown voltage/
comeback voltage
(176V±4V)/ (184V±4V)(176V±4V)/ (184V±4V)(176V±4V)/ (184V±4V)(176V±4V)/ (184V±4V)Load < 1000W
(152V±4V)/ (160V±4V)(160V±4V)/ (168V±4V)(152V±4V)/ (160V±4V)(160V±4V)/ (168V±4V)Load>= 1000W
DC protection
Overcharge
protection/
comeback voltage
(249.6V±4V) / (216V±4V) 
Leakage current< 500uA 
Over discharge
protection
14.5hCould be set by software
Battery test
Battery weakYES 
Battery faultYES 
Charger
Output voltage(219.2±3)VDC 
Charge time7 hours to 90% capacity    
Charge current1A5.5A1A5.5A 
Interface
Alarm silenceYES 
DC power
turn-on
YES 
Automatically
retransfer
YES 
Audio alarm
Battery modeBeep/4s 
Battery low/
charger fault
Beep/1s 
UPS faultContinue beep 
OverloadBeep/1s 
Bypass modeBeep/2Min 
L/N inverseBeep/2Min 
Communication
RS232 interfaceYES 
Intelligent slotYES 
Monitor softwareAppending with UPS 
Cooling
Force air cooling
Display
LCD/LED
displays UPS
status
     
Environment
Work
temperature
0ºC~40ºC 
Altitude<1000m 
Audible noise≤55dB≤60dB 
Storage
temperature
-15ºC~45ºC 
Work humidity20%~95% 
Standard
EMS
ESDIEC61000-4-2Level4
RSIEC61000-4-3Level3
EFTIEC61000-4-4Level4
SurgeIEC61000-4-5Level4
EMI
ConductedEN55022Class B
RadiatedEN55022Class B
Safety
SafetyGB4943-2001/IEC62040-1 
Transportation
Drop testGB-T4857-18 
Vibration testB-WR1-129(GB-T14715-93) 
Machinery features
Size
Outline dimension and net weight
L*W*H(mm)533*260*560425*190*328533*260*560533*260*501 
Net weight
(Kg)
55kg12.2kg62kg21kg 
Optional functions
60HzOptionalSet by software
Converter modeOptionalSet by software
ECOOptionalAvailable and set by software
EPOOptional 
LCD displayOptional 







Product Tag:
Related categories:
Scroll to Top