Model | ZDMS0.8/20S-LZII ZDMS0.8/20S- LZII Ex | ZDMS0.9/30S- LZII ZDMS0.8/20S- LZII- Ex | ZDMS0.8/40S- LZII ZDMS0.8/40S- LZII-Ex | ZDMS0.8/50S- LZII ZDMS0.8/50S- LZII-Ex | ZDMS1.0/60S- LZII ZDMS1.0/60S- LZII-Ex | |
Rated Flow | 20L/S | 30L/S | 40L/S | 50L/S | 60L/S | |
Rated Working Pressure | 0.8Mpa | 0.9Mpa | 0.8Mpa | 0.8Mpa | 1.0Mpa | |
Maximum Working Pressure | 1.2Mpa | 1.2Mpa | 1.2Mpa | 1.2Mpa | 1.2Mpa | |
Mounting Height | 8~15M | 8~22M | ||||
Maximum Protection Radius | 50M (Radius of the jet: 56M) | 55M (Radius of the jet: 62M) | 60M (Radius of the jet: 67M) | 65M (Radius of the jet: 73M) | 70M (Radius of the jet: 78M) | |
Nominal diameter | DN80mm | DN100mm | ||||
Working Voltage | 100~242V AC | |||||
Power Consumption | Ready mode:10W. Action mode:100W | |||||
MODBUS RTU | CAN | |||||
Positioning Time | ≤60S | |||||
Fire extinguishing time | ≤3 mins | |||||
Environment temperature | -10ºC~55ºC | |||||
Horizontal Rotation Angle | 360° | |||||
Vertical Rotation Angle | -90°~ +30° | |||||
Overall Dimensions (L×W×H) | 360mm×230mm×300mm | 390mm×400mm×310mm |
Function | Parameter | ||
Manual, AUTO: Manual / Automatic switching. | Select spraying direction in manual mode: up, down, left and right. | Model: CZP-1 | Working voltage:AC110V~AC242V. |
Electric valve status:ON/OFF | Column,FOG: Water monitor jet mode, columnar and foggy. | Rated power:6W. | Way to install:Wall mounted. |
Fire pump start and stop buttons:Fire pump ON, OFF. | Alarm signal input and output. | Ingress Protection: IP67 | |
Indicator: Automatic, manual, fire alarm, valve, fire pump, fault, communication. | Communication mode: CAN. | ||
One field operation panel control one water monitor / one field operation panel controls multiple water monitor s (the number of waters monitor s cannot exceed 32pcs). | Dimensions:( L ) 276×( W ) 190×( H )90(mm). Weight: 1.2kg. |
Working Voltage | 100~242V AC | Model: DKX-1 | Ingress Protection | IP67 |
Operating current | Ready mode:100mA, Action mode:1A | Operating temperature | 4ºC~55ºC | |
MODBUS RTU | CAN | Dimensions: 276( L )×190( W )×90( H )(mm). Weight: 1.0kg. | ||
Switching value signal input, output, electric valve, pressure switch, water flow indicator and signal valve feedback signal input port. DC24V power output port (external UV flame detector). |