Hfc-236fa Indirect Electric Equipment Fire Suppression Systems with Control Panel

Min.Order: 10
Product origin: Hangzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 220 ~ 240

Description
 
1.BACKGROUND
The characteristics of electrical fire hazards are the distribution, persistence and concealment of fire hazards. Due to the wide distribution of electrical systems and long-term continuous operation, electrical lines are usually laid in concealed places (such as ceilings, cable trenches), and are not easy to be detected by the fire alarm system at the initial stage of a fire, nor are they easy to observe with the naked eye. The danger of electrical fire is also closely related to the electricity consumption. When the electricity load increases, it is easy to cause electrical fires due to overcurrent.
 
The casualties, property losses and social shocks caused by the fire are huge. Electrical fires mainly occur in buildings, where people are close, evacuation is difficult, and smoke is not smoothly exhausted. It is very easy to cause serious accidents of mass death and injury.
2.PRINCIPLE OF SYSTEMS(Direct type)
PRI-SAFETY electric equipment fire suppression systems have been specifically designed to protect electric equipment and put out electric fires caused by leakage electric(class E fire) quickly and efficiently.
 
These self contained pneumatic systems require no external energy or power supply. Upon flame impingement or heat, the pressurized detection tubing will burst and activate the cylinder valve to open and release the extinguishing agent.
 
PRI-SAFETY electric equipment fire suppression systems are specifically designed to extinguish fires of electric panel, battery bay, control panel, electric equipment etc. It is developed to prevent damage of equipment, records, people and other assets that are vital to a business.

3.Product drawing


The temperature sensor send temperature signal to control panel, the control panel can indicate the temperature at anytime, once temperature reach 100 ºC, the fire alarm was activated. Once the temperature reach 140ºC, control panel will send signal to electric valve to open it. Then the agent was discharged from dischange tube and nozzles. On the control panel, there is a manual button and test button, reset button, in Emergency pushing the manual button can activate the fire system too.

4.DIAGRAM


5.COMPONENTS

6.PRODUCT ADVANTAGES
*Simple, high quality and well engineered system. Easy to install.
*Fast, automatic actuation.
*We use gas instead of water to put out the fire without causing damage.
*When a fire occurs, the system will first detect it and then feedback control the fire extinguishing system to turn on and       extinguish the fire within 10 seconds.
*Remaining operational during power interruptio.
*There is no need for manual close fire fighting.
7. PRODUCT PARAMETERS
Items No.
EFS-01EFS-02EFS-06EFS-09EFS-12EFS-25
Capacity1Kg2Kg6Kg9Kg12Kg25Kg
Out-Dia.(mm)90110160180180257
Cylinder Length(mm)270302450485621775
Volume(L)1.29L3.8L7.8L10.5L16L35L
Extinguishing AgentFM200FM200FM200FM200FM200FM200
Working Pressure(bar)14bar14bar14bar14bar14bar14bar
Test Pressure(bar)27bar27bar27bar27bar27bar27bar
Cylinder MaterialST12 or SS304ST12 or SS304ST12 or SS304ST12 or SS304ST12 or SS304ST12 or SS304
Discharge Pipeφ6mm SS304φ6mm SS304φ12mm SS304φ16mm SS304φ16mm SS304φ16mm SS304
CertificateCE markedCE markedCE markedCE markedCE markedCE marked
Activation Temperature Detection Tube140ºC140ºC140ºC140ºC140ºC140ºC
8.CERTIFICATION

9. APPLICATION
1kg---For 0.1~0.5m Electric Panel
2kg---For 0.5-1m Electric Panel
9kg---For 1.5-2m Electric Equipment
6kg---For 1-1.5m Electric Panel
12kg--- For 2-2.5m Electric Room
25kg--- For 2.5~3.5m Electric Room
Bigger capacity could be customized
Electric Panel,Battery Bay,Control Panel,Electronic Equipment,Server Panel/Room
 
10. PACKING&SHIPPING

 

11. ABOUT US
 

12. EXHIBITION

13. FAQ

Q1. May I get a sample before placing an order?
A1. Yes, no problem.

Q2. Are your company PRI-SAFETY a manufacturer or trading company?
A2. We are a manufacturer.

Q3. Can you print our logo on products?
A3. Yes, no problem. We also support OEM.

Q4. How long does it take to delivery?
A4. In 30-45 days after receipt of 30% deposit.

Q5. What's your MOQ?
A5. Fire extinguisher is class2.2 Dangerous Goods, it should be loaded with full container.
But if you have another goods shipping together or you need empty type, our MOQ is 100 sets.
 
Q6.What's your Payment Term?
A6.We support T/T,L/C,Credit Card,Western Union etc.
Product Tag:
Related categories:
Scroll to Top