Key Parameters:
· CE/CB/ISO9001/CCC certificates;
· Rated voltage:230VAC;
· frequency:50/60Hz;
· Rated current:3,6,10,16,20,25,32A;
· Mechniacal life:20,0000times;
· Flame-redardant:PA66 nylon material;
· Protection degree:IP20;
· With over load/short circuit protection;
· Standard:IEC60898;
· Enduring tem.30°C
· Breaking Capacity:3KA;
· Lighting/Motor protection optional
Application
DZ30-32(DPN) series(phase line+ neutral line) circuit breaker is suitable to the single phase residual circuit of AC50or60Hz,rated voltage 230V,protecting the circuit from over load and short circuit. The product has high breaking capacity, volume small, live wire ,null wire are
cut at the same time to avoid the inversed grafting of live and null wire or danger caused by the voltage between zero wire and earth.
It is the ideal power distribution switch for the present residence.It conforms to standard IEC60898-1&GB10963.1.
Technical Parameters
Model | Rated Voltage(V) | Poles(P) | Rated Current in(A) | Rated Short Circuit Breaking Capacity | Mechanical life | |
test expected current(A) | test power factor | |||||
DZ30-32 | 230 | 1P+N | 3,6,10,16,20,25,32 | 3000 | 0.65-0.70 | 10000 |
Tripping Characteristics
Test current(A) | Rated current(A) | Requested time | Result | Start station | Remark |
1.13In | All | t≥1h | Don't trip | Cool | |
1.45In | All | t<1h | Trip | Heat | Current ascends the requested value stably in 5s |
2.55In | All | Is<t<60S | Trip | Cool | Auxiliary switch closed, power is on |
5In | All | t≥0.1S | Don't trip | Cool | Auxiliary switch closed, power is on |
10In | All | t<0.1S | Trip | Cool | Auxiliary switch closed, power is on |