Adw220-D10-4s Smart Iot Meter DIN Rail Energy Meter Measuring 3 Phase Circuit Electric Parameters

Min.Order: 1
Product origin: Shanghai, China
Infringement complaint: complaintComplaint
US$ 304.5

Description
Overview
The power Internet of Things combines various electrical measurement, metering, non-electricity measurement, protection and other instruments and equipment in the traditional power industry with the current popular Internet of Things technology, breaking the traditional networking, debugging, and application methods, making it more convenient for users to use related platforms Visually see the comprehensive information of the target site. ADW series has three types of products: ADW200, ADW300, and ADW400, which correspond to various industrial applications.
ADW210 series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits,Up to four three-phase loop current inputs can be connected simultaneously.It Can measure voltage and current,power,power factor, phase angle, unbalance, harmonic and other parameters.
 
Function
Measurement of all electric parameters of N(1,2,3,4)channels three-phase circuit.
Current transformer external.
1.Three phase voltage,current,zero-sequence current,frequency;
2.Three phase power,total power(active,reactive,apparent);
3.Voltage and current phase angle,voltage and current imbalance;
4.Voltage,current total harmonic and 2nd-31st harmonic;
5.Record of extreme values of voltage,current and power in current month and last month;
6.Maximum current,power demand and real-time current,power demand;
7.200 event records,recording the action of DIDO;Support over-voltage,over-current,phase failure,DI linkage and other alarm output;
8.The rate of 4 time zones and 14 time periods can be set;
9.Four quadrant electric energy,12-month multi rate electric energy statistics;
10.31 days four quadrant and multi rate electric energy freezing;
11.Active energy class 1.0,and reactive electric energy class 2.0;
12.Standard function:2DI/2DO,RS485,1 way active pulse output(corresponding circuit can be switched);
13.Equipped with N(1,2,3,4)groups of open type current transformer,each group with 3 current transformer;
14.ADW with Lora wireless communication.
Option
MTL
12 external NTC temperature measurement+4 residual current measurement
External expansion module connected with ADW through RJ45 interface
MK
12DI+4DO

Technical parameters
Type
ADW220-D10/4S
Auxiliary power
AC/DC 85~265V;consumption≤10VA;
input
Frequency
45~65Hz;
Voltage
AC 3×220V/380V;Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s;
Power consumption:≤ 0.5VA;
Current
AC 5A,100A,400A,600A;(External opening transformer)Overload: 1.2 times of rated value (continuous);
10 times of rated value / 1s;Power consumption:≤ 0.5VA
measurement accuracy
Frequency 0.05Hz, voltage and current 0.5 level, active electric energy level 1, reactive electric energy level 2;2-31 times
harmonic accuracy: ± 1%;
Features
Pulse output
Output mode: optocoupler pulse with open collector;
Communication
RS485,Modbus-RTU;Baud rate 1200~38400;
Switching
input
Dry contact input,Built in power supply;
output
Output mode:Relay normally open contact output;
contact rating:AC 250V/3A DC 30V/3A;
Switching Module
Power
RJ45 interface,DC 12V,Power consumption≤1W;
Communication
RJ45 interface,Modbus-RTU;(Communication with the main Part)
Switching input
Dry contact input,Built in power supply;
Switching output
Output mode:Relay normally open contact output;
contact rating:AC 250V/3A DC 30V/3A;
Temperature and leakage module
Power
RJ45 interface,DC 12V,Power consumption≤1W
Communication
RJ45 interface,Modbus-RTU;(Communication with the main Part)
temperature measurement
-20~100ºC;
Leakage measurement
10~3000mA;
measurement accuracy
temperature ±2ºC,Leakage1.0%;

Typical connection

Products size

Packing&Delivery     

About company     

Contact     
Product Tag:
Related categories:
Scroll to Top