Rated System Voltage (kV) | Type | Section Length (mm) | Arcing Distance (mm) | Creepage Distance (mm) | Specified Cantilever Load (kN) | Specified Tensile Load (kN) | Lightning Impulse Withstand Voltage (kV) | Power Frequency Withstand Voltage (kV) | |
Dry | Wet | ||||||||
10 | FZS-10/5 | 215 | 125 | 290 | 5 | 70 | 75 | 35 | 28 |
35 | FZS-35/5 | 620 | 480 | 1200 | 5 | 70 | 265 | 125 | 100 |
35 | FZS-35/8 | 620 | 480 | 1200 | 8 | 70 | 265 | 125 | 100 |
66 | FZS-66/5 | 830 | 630 | 1800 | 5 | 70 | 410 | 230 | 185 |
66 | FZS-66/8 | 830 | 630 | 1800 | 8 | 70 | 410 | 230 | 185 |
110 | FZS-110/5 | 1270 | 1025 | 2900 | 5 | 70 | 550 | 285 | 230 |
110 | FZS-110/10 | 1270 | 1025 | 2900 | 10 | 70 | 550 | 285 | 230 |
10 | FPQ-10/3 | 285 | 205 | 450 | 3 | 10 | 110 | 50 | 40 |
10 | FPQ-10/5 | 285 | 205 | 450 | 5 | 10 | 110 | 50 | 40 |
Order Information: 1.Voltage grade; 2.Specified mechanical load; 3.Creepage distance; 4.Power frequency withstand voltage; 5.Lightning Impulse Withstand Voltage; 6.Insulation distance; 7.Coupling type Ps. Different design could be supplied as customer requirements |