model project | TH48D50NZ-S | |
Output current (a) | 50 | |
Power (KW) | 2.9 | |
input voltage Scope (VAC) | minimum value | 93 (enter 165 to reduce power) |
typical value | 20 (286-300 limited power output | |
maximum | 264 | |
Output adjustable norm Circumference (VDC) | minimum value | 43.2 |
typical value | 48 | |
maximum | 58 | |
Voltage stabilization accuracy | ≤±0.5% | |
Steady flow accuracy | ≤±0.5% | |
Charger efficiency (efficiency) | ≥94% | |
Power factor | 0.99 (more than half a year) | |
Maximum audible noise (dB) | 55 | |
Storage temperature (ºC) | minimum value | -40 |
typical value | 25 | |
maximum | 60 | |
Working ambient temperature (ºC) | minimum value | -25 |
typical value | 25 | |
maximum | 55 | |
Parallel uneven mobility | <±3% | |
Start-up delay (seconds) | 3S-8S | |
ripple coefficient | 200mV | |
Load level | Class I (100%) works continuously at rated output current. | |
Automatic current limiting characteristic | When the output current exceeds the set value of the output current limit, the output current will be constant and will not increase. | |
Output overvoltage protection | Output voltage exceeds 63±5VDC, which automatically stops output to prevent equipment damage. | |
Output short-circuit protection characteristics | When the output is short-circuited, the module will protect itself to prevent damage, and it can automatically resume working after troubleshooting. | |