Xhdj706 Earth Resistance Soil Resistivity Tester 2, 3, 4 Wire Method Ground Resistance, Soil Resistivity, Ground Voltage Measurement

Min.Order: 1
Product origin: Xi'an, Shaanxi, China
Infringement complaint: complaintComplaint
US$ -1

Description


Product Introduction

XHDJ706 Earth Resistance Soil Resistivity Tester is specially designed and manufactured for measuring earth resistance, soil resistivity, earth voltage, AC voltage. Adopting the latest digital and micro-processing technology, precise 4-pole, 3-pole and simple 2-pole method for earth resistance measurement, importing FFT and AFC technology, with a unique function ofanti-interference capability and the ability to adapt to the environment, consistency of repeat testing, to ensure high precision, high stability and reliability for prolonged measure, which is widely used in electric power, telecommunications, meteorology, oil field, construction, lightning protection, industrial electrical equipment and other earth resistance, soil resistivity, earth voltage, AC voltage measurement.

XHDJ706 Earth Resistance Soil Resistivity Tester is composed of host machine, monitoring software, testing wires, auxiliary ground probes, communication wires and others. The large LCD display of host machine is with blue backlight and bar graph indicating that can be seen clearly. At the same time it can store 300 sets of data, fulfilling historical inquiry and online real-time monitoring through monitoring software, dynamic display, alarm indicator, and with the functions like historical data access, reading, preservation, report forms, printing and so on.

XHDJ706 Earth Resistance Soil Resistivity Tester also named: Precise Earth Resistance Tester, 4-pole Earth Resistance Tester, 2/3/4-pole Earth Resistance Tester, Soil Resistivity Tester.

 
II.Technical Specifications

1. Base Conditions and Working Conditions

Influence ItemsBase ConditionWorking ConditionsRemark
Ambient Temp23ºC±1ºC-10ºC-40ºC----
Ambient Humidity40%-60%<80%----
Working Voltage9V±0.1V9V±1.5VrC,rP
Auxiliary Earth Resistance<100Ω<30kΩ----
Interference VoltageNo<20V----
Interference CurrentNo<2A 
Electrode Distance when measuring Ra>5da>5d----
Electrode Distance when measuring ρa>20ha>20h----

 

2. General Specification

FunctionMeasurement of 2/3/4-pole earth resistance, soil resistivity, earth voltage, AC voltage
Power SupplyDC 9V(Zi-Mn dry battery R14S 1.5V 6 PCS, continuous standby for 300 hours )
Measurement RangeEarth Resistance: 0.00Ω-30.00kΩ
Soil Resistivity: 0.00Ωm-9000kΩm
Earth Voltage:0V~600V
Measuring ModePrecise 4-pole measurement, 3-pole measurement, simple 2-pole measurement
Measuring MethodEarth Resistance: rated current change-pole method, measurement current 20mA Max
Soil Resistivity: 4-pole measurement (Wenner method)
Earth Voltage: average rectification(between P(S)-ES)
Test Frequency128Hz/111Hz/105Hz/94Hz(AFC)
Short-circuit Test CurrentAC 20mA max
Open-circuit Test CurrentAC 40V max
Test Voltage WaveSine wave
Electrode Distance RangeCan be set 1m-100m
ShiftEarth resistance: 0.00Ω-30.00kΩ, automatic shift
Soil Resistivity: 0.00Ωm-9000kΩm, automatic shift
BacklightBlue screen backlight, suitable for dim places
Display Mode4-digital super-large LCD display, blue screen backlight
Measuring IndicatorDuring measurement, LED flash indicator, LCD count down display, progress bar indicator
LCD Frame Dimension128mm×75mm
LCD Window Dimension124mm×67mm
DimensionL×W×H: 215mm×190mm×95mm
Standard Test Wire4 wires: each for red 20m, black 20m, yellow 10m, and green 10m
Simple Test Wire2 wires: 1pcred 1.6m and 1pc black 1.6m
Auxiliary Earthing Rod4 wires: Φ10mm×150mm
Measuring RateVoltage to ground: about 3 times/second
Earth resistance, soil resistivity: about 5 seconds/time
Measuring TimesOver 5000 times (Short-circuit test, interval time should be at least 30 seconds)
Circuit Voltagebelow AC 600V
USB InterfaceWith USB interface, Support software supervision, storage data can be uploaded to computer, saved or printed.
USB Communication WireOne piece of USB communication wire, length 1.5m
Data Storage300 sets, "MEM" icon storage indicator, display "FULL" icon to indicate storage is full
Data HoldData hold function: "HOLD" icon display
Data ReadData read function: "READ" icon display
Overflow DisplayExceeding measuring range overflow function: "OL" icon display
Interference TestRecognize interference signal automatically, "NOISE" icon display when interference voltage exceeds 5V
Auxiliary Earthing TestCan measure auxiliary earth resistance, 0.00KΩ-30kΩ(100R+rC<50kω<>, 100R+rP<50kω)<>
Alarm FunctionWhen measuring value exceeds alarm setting value, there is "Toot-toot-toot" alarm sound
Battery VoltageWhen battery voltage decreases to about 7.5V, battery voltage low icon will display, reminding to replace battery.
Power ConsumptionStandby: about 20mA(Backlight shut off)
Boot and with backlight: about 45mA(25mA without backlight)
Measurement: about 100mA(Backlight shut off)
WeightTotal weight: 4.5kg(including package)
Tester: 950g(including battery)
Tesing wires: 1560g
Auxiliary earthing rods: 935g(4pcs)
Working Temperature & Humidity-10ºC-40ºC, below 80%rh
Storage temperature & humidity-20ºC-60ºC, below 70%rh
Overload ProtectionMeasuring earthresistance: between each interfaces of C(H)-E,P(S)-ES,AC 280V/3 seconds
Insulation ResistanceOver 20MΩ(between circuit and enclosure it is 500V)
Withstanding VoltageAC 3700V/rms(Between circuit and enclosure)
Electromagnetic FeaturesIEC61326(EMC)
Protection TypeIEC61010-1(CAT 300V,CAT IV 150V,Pollution 2), IEC61010-031, IEC61557-1(Earth resistance), IEC61557-5(Soil resistivity), JJG 366-2004
<50kω<><50kω)<>

 

3. Intrinsic error and performance indicators under base conditions

CategoryMeasurement RangeIntrinsic ErrorResolution
Earth Resistance
(R)
0.00Ω-30.00Ω±2%rdg±3dgt0.01Ω
30.0Ω-300.0Ω±2%rdg±3dgt0.1Ω
300Ω-3000Ω±2%rdg±3dgt
3.00kΩ-30.00kΩ±4%rdg±3dgt10Ω
Soil Resistivity
(ρ)

 
0.00Ωm-99.99ΩmAccording to the precision of R
(ρ=2πaR
a:1 m-100m,
π=3.14)
0.01Ωm
100.0Ωm-999.9Ωm0.1Ωm
1000Ωm-9999Ωm1Ωm
10.00kΩm-99.99kΩm10Ωm
100.0kΩm-999.9kΩm100Ωm
1000kΩm-9000kΩm1kΩm
Earth VoltageAC 0.0-600V±2%rdg±3dgt0.1V

Note: 1. AtrC max or rP max, additional error≤±3%rdg±5dgt.
(rC max: 4kΩ+100R<50kΩ, rP max: 4kΩ+100R<50kΩ)
2. Under5V interference voltage, additional error≤±5%rdg±5dgt.



 












Product Tag: