Xgn66-12 Box Type Fixed AC Metal Enclosed Switchgear

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 1000 ~ 30000

Description
GENERAL

Xgn66-12 box type fixed AC metal-enclosed switchgear (hereinafter referred to as simple switchgear) is a new generation of a complete set of high-voltage electrical appliances designed and developed by our factory, which meets the requirements of the national standard GB3906 "3 ~ 35kV AC metal-enclosed switchgear" and the Ministry of electric power DL / t404 "technical conditions for ordering indoor AC high-voltage switchgear", It also meets the requirements of the international standard iec60298 AC metal-enclosed switchgear and control equipment above 1kV and below 25kV.

This product has absorbed the advanced technology of foreign countries and is designed and developed for the problems of high accident rates and a large volume of existing similar switchgear in China. It has the advantages of small cabinet volume (only 50% of the volume of an ordinary switch cabinet), good circuit breaker performance, high reliability, and a reliable and simple "five prevention" interlocking mechanism.


MODEL AND MEANING


NORMAL SERVICE CONDITIONS

a. Ambient temperature: no more than + 40 ºC; At least - 15 ºC;
b. Environmental humidity: relative humidity: the daily average value shall not exceed 95%, and the monthly average value shall not exceed 90%; Water vapor pressure: the daily average value shall not exceed 2.2kpa, and the monthly average value shall not exceed 1.8ka;
c. Altitude: when the product is applicable to 12kV, the altitude shall not exceed 1000m; When the product is applicable to 7.2kV, the altitude shall not exceed 3000m
d. The surrounding air is not obviously polluted by dust, smoke, corrosive or combustible gas, vapor or salt mist;
e. Vibration or ground motion from outside the switchgear and control equipment is negligible;
f. The amplitude of electromagnetic interference induced in the secondary system shall not exceed 1.6kv;

Special use conditions
The user and the manufacturer shall negotiate when using under normal environmental conditions exceeding GB / t11022 and this instruction manual.

 

TECHNICAL PARAMETERS

 Switch Cabinet Technical Parameters Table 1
NoItemUnitParameters
1Rated Voltage
kV
 
12
2Rated Insulation Level1 min Power Frequency Withstand Voltage42
Lightning Impulse Withstand Voltage75
3Rated FrequencyHz50
4Rated Current of Main BusbarA630,     1250
5Rated Short-Circuit Breaking Current 
kA
 
20,   25,    31.5
6Rated Short-Time Withstand Current20,   25,    31.5
7Rated Withstand Current (Peak Value)50,   63,    80
8Rated Short-Circuit Breaking Current50,   63,    80
9Protection Level IP3X
10Outline Dimension (width x depth x length)mm900 x 950 x 2300


Isolation Switch Technical Parameters Table 2
No.ItemUnitParameters
GN19 - 12C/630GN19-12C/1250
GN30 - 12/630GN30 - 12/1250
GN30 - 12D/630GN30 - 12D/1250
1Rated VoltagekV10
2Rated CurrentA6301000
34s Rated Short-Time Withstand CurrentkA2031.5
4Rated Withstand Current (Peak Value)kA5080
5Rated Insulation Level1 min Power Frequency Withstand VoltagekV
 
42
Lightning Impulse Withstand Voltage75
 

Vacuum Circuit Breaker Technical Parameters Table 3
NoItemUnitParameters
1Rated Voltage
kV
 
12
2Rated Insulation LevelPower Frequency Withstand Voltage75
Lightning Impulse Withstand Voltage42
3Rated FrequencyHz50
4Rated Current of Main BusbarA630,     1250
5Rated Short-Circuit Breaking Current 
kA
 
20,   25,    31.5
6Rated Short-Time Withstand Current20,   25,    31.5
7Rated Withstand Current (Peak Value)50,   63,    80
8Rated Short-Circuit Breaking Current50,   63,    80
9Rated Back-to-Back Capacitor Bank Breaking CurrentA400
10Rated Operating Order O-0.3s-CO-180s-CO
11Mechanical LifeTimes20000
12Rated Short-Circuit Breaking Current Breaking TimesTimes50
11Main Circuit ResistanceμΩ≤ 40

OUTLINE DIMENSION AND STRUCTURE








 