Technical parameter | Value | |
Measuring range | Temperature | -40.0ºC~99.9ºC |
Humidity | 0%RH~99%RH | |
Precision | Temperature | ±1ºC |
Humidity | ±5%RH | |
Transmitting output | DC4~20mA or DC0~20mA | |
Set range of controlling parameter | Heating for Temperature rising | -40.0ºC~40.0ºC |
Blowing for temperature decreasing | 0.0ºC~99.9ºC | |
Humidity control | 20%RH~90%RH | |
output contact capacity | 5A/AC250V | |
Start/stop gap | 5 | |
Communication port | RS485,MODBUS(RTU)treaty | |
Auxiliary power | Voltage | AC/DC85-265V |
Consumption | Basic power consumption(≤0.8w) +relay power consumption (each channel≤0.7w) | |
Insulation resistance | ≥100MΩ | |
power-frequency with stand voltage | power with shell, touchable metal parts/power with other terminal group 2kV/1min(AC,RMS) | |
average work time without stop page | ≥50000 hours | |
Working condition (controller) | Temperature | -20ºC~+60ºC |
Humidity | ≤95%RH,without condensation and corrosive gas | |
Altitude | ≤2500m | |
Start/stopgap:In the control process, for the execution part (heater or fan), the difference between starting temperature (humidity) and stopping temperature(humidity). |