Power 3 Phase 750kw 60Hz Cummins Stamford Open Type Diesel Generator

Min.Order: 1
Product origin: Fuzhou, Fujian, China
Infringement complaint: complaintComplaint
US$ 67000 ~ 77000

Description
PRODUCT DESCRIPTION 
 
Frequency: 50HZ;Rotating speed: 1500Rpm
ModelPower(KW)Capacity(KVA)Rated current(A)Engine ModelCopy Stamford Type
BS-C252025364B3.9-G1BS184F
BS-C40324057.74BT3.9-G2BS184J
BS-C7056701014BTA3.9-G11BS224G
BS-C856885122.76BT5.9-G1BS224G
BS-C12096120173.26BTA5.9-G2BS274D
BS-C1401121402026BTAA5.9-G2BS274E
BS-C160128160230.96CTA8.3-G1BS274F
BS-C275220275396.9NTA855-G1ABS314D
BS-C350280350505NTA855-G2ABS314E
BS-C400320400577.4NTAA855-G7ABS354C
BS-C450360450649.5KTA19-G3BS354C
BS-C500400500721.7KTA19-G4BS354D
BS-C600480600866KTAA19-G6BS354E
BS-C7506007501082.6KTA38-G2BS404B
BS-C8006408001154.7KTA38-G2BBS404C
BS-C9007209001299KTA38-G2ABS404D
BS-C80080010001443.4KTA38-G5BS404E
BS-C1250100012501804.3KTA50-G3BS404G
      
Frequency: 60HZ;Rotating speed: 1800Rpm
ModelPower(KW)Capacity(KVA)Rated current(A)Engine ModelCopy Stamford Type
BS-C29232941.54B3.9-G1184E
BS-C43344361.34BT3.9-G1184H
BS-C63506390.24BTA3.9-G2224D
BS-C806480115.54BTA3.9-G11224F
BS-C947594135.36BT5.9-G2224G
BS-C125100125180.46BTA5.9-G2274D
BS-C150120150216.56BTAA5.9-G2274E
BS-C188150188270.66CTA8.3-G2274F
BS-C250200250360.9NT855-GA274J
BS-C394315394568.3NTA855-G3314E
BS-C438350438631.5KTA19-G2314F
BS-C513410513739.8KTA19-G3354C
BS-C625500625902KTAA19-G5354D
BS-C688550688992.3KTAA19-G6A354E
BS-C7756207751118.6KT38-G354F
BS-C9067259061308KT38-G2404C
BS-C100080010001443.4KT38-G2A404D
More specific parameters to choose and we can provide original Stamford generator.
Genset Model:BS-C938
Prime Power (kw/kva)750 / 938Standby Power(kw/kva)825 / 1031
Voltage (v)230 / 400Rated Speed (rpm)1800
Frequency (Hz)60Rated Current (A)1155
Connection:3 phase 4 wirePower Factor:0.8
Engine Model:KTA38-G2BAlternator Model:LVI634B
Net Weight (kgs)-Open7700kgsNet Weight (kgs)-Silent8800kgs
Dimensions (mm)-Open4400x2060x2620Dimensions (mm)-Silent5000x1850x2160
Engine Parameter:
Manufacturer/Model:               Aspiration:                              Fuel System:        
Cylinder numbers
Displacement:
Bore x Stroke
Compression Ratio:
Max. Power:
Governing System:
CCEC, KTA38-G2B, 4-cycle
Turbo, Air / water cooling

PT Fuel Pump, EFC
12 cylinders in "V"
37.8L
159 x 159 mm
14.5 : 1
920KW/1233HP
Electronic
Exhaust System
Exhaust gas flow:
Exhaust temperature:
Max. Allowed Back Pressure:
 3290 L/s
 485 ºC
  10 KPa
Intake System
Max. Allowed Pressure:
with Dirty Filter Element
with Normal Duty Air Cleaner and Clean Filter Element
with Heavy Duty Air Cleaner and Clean Filter Element
Air Flow:

6.22 kPa
2.49 kPa

3.74 kPa

1251 L/s
Fuel System
     100% Load (Prime):
75% Load(Prime):
50% Load (Prime):
382L/h
294L/h
208L/h
Lube System
Oil Capacity:
Total system capacity(L):
Oil Pressure at rated speed:
114 L
35.7 L
296-483 kPa
Cooling system
Coolant Capacity(Engine only):
Thermostat:
Max. Water Temperature:
118 L
82-94ºC
104ºC
Alternator Parameter:        Basic Information
The alternators meet the standards of:
GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350
Technical Data:
Manufacturer:
Phases:
Connection:
Bearing numbers:
Power Factor:
Protection Class:
Altitude Condition:
Excitation:
Insulation class/Temp. rise class:
Tel. Influence Factor TIF:
Tel. Harmonic Factor THF:
Steady State Voltage Regulation:
Alternator Capacity:
Efficiency:
Cooling Air Flow:
  Stamford, LVI634C 
 3
  3 phase 4 wire, Y type
  1
 0.8
 IP23
 1000M
 Brushless, self-excitation
  H / H
  <50
 <2%
 ±1%
 1000KVA
 93.7%
 1.312 m³/s
 
PRODUCT SHOWS 




 
PRODUCT ADVANTAGE 
 
(1)The silent canopy we use cold-rolled sheet, all positions are stronger.
 
(2)Our spraying plastics all go through pre-treatment of pickling and phosphating, so that the surface of the
  
   painting will not change color even if placed outside for five years.

 
(3)Canopy color painted by customer's requirement.
 
(4)Strict test including 50% load,75% load,100% load and 110% Load .
 
(5)Forklift mouth in base frame for easy loading and discharging.
 
(6)Logo made by customer's requirement if order quantity ≥10units or a full container.


FAQ 
Q: Do you offer OEM service?
A: Yes
Q: What is your payment term?
A: 30% T/T in advance, the rest payment before shipment.  Or irrevocable L/C.
Q: What is your lead time?
A: About 30 days after receiving deposit or original L/C.But if your order with some special design, then the
   delivery time is longer.

Q: What certificates do you have?
A: We have CE, ISO. And we can apply for specific certificate for different country such as SONCAP for Nigeria,
    CIQ for Egypt, SASO for Saudi Arabia, etc

Q:What is your MOQ?
A: Above 1pc
Q. Which port do you often use when export?
A: Fuzhou Port, or as customer request.
Q.How to choose the power?
A.:Collect all power of your equipments,take the current into your consideration.
Q.What is the difference between Prime power and Standby power?
A.:Prime power is 12hours continous power,one hour 10% over load in every 12 running hours is allowed.
Standby power is the limit value of maximum output for emergency use. Overloading is prohibited
Q.What about the warranty
Guarantee for one year or 1000 hours (accord to whichever reach first) from ex-factory date.During the guarantee period,
our company will provide the free easy damaged spare part for problems caused by our quality of production or raw material
except the damageable spare parts of diesel engine caused by customer's incorrect man made operation.After expiration,
our company provides cost parts maintenance for gen-set.

 
CONTACT US 

Product Tag:
Related categories:
Scroll to Top