Rated supply voltage | P-P: AC 3× 208--3× 440V; P-N: AC 3× 120--3× 254V |
Rated supply working voltage range | P-P:AV 166V--528V;P-N:AC 96V-329V |
Rated supply frequency | 50Hz/60Hz |
Voltage measurement error | ≤1% (Entire setting range) |
Delay error | ±10%+0.1s |
Rated working voltage selection | M440:208-220-230-240-380-400-415-440(V)(P-P) M254:120-127-132-138-220-230-240-254(V)(P-P) |
Measuring range | AC 166V--528V; AC 96V--329V |
Measurement frequency range | 45Hz-65Hz |
Vlotage threshold range | 2%-20% |
Unbalance threshold range | 5%-15% of rated voltage |
Fixed hysteresis rate | 2% |
Action delay range | 0.1s-10s |
Reset delay range | 0.1s-10s |
Knob setting accuracy | 1% scale value |
Phase failure and phase sequence | ≤0.5s |
Rated insulation voltage | 440V |
Contact configuration capacity(A) | 2 C/O 8A;1 C/O+1 C/O 5A |
IP Class | IP20 |
Class of pollution | 3 |
Electrical Life | 105 |
Mechanical life | 106 |
Altitude | ≤2000m |
Allowable relative humidity | ≤50%(40ºC)(No condensation) |
Use category | AC-15 |
Contact capacity | Ue/le:250V/1.5A |
Output type | 2 C/O;1C/O+1 C/O |
DIN rail Standard | Width 35mm(IEC/EN60715) |