ADL400 din rail energy meter adopts DIN35mm din rail installation with LCD display, it can measure electric parameters and has energy pulse output, RS485 communication, which has the advantages of small size, high precision, good reliability, and convenient installation.
Voltage | Nominal voltage | AC 3*100V, 3*380V, 3*57.7/100V, 3*220/380V | ||
Nominal frequency | 50Hz | |||
consumption | <10VA | |||
Current | Maximum current | 80A | ||
Starting current | 0.01A | |||
Consumption | <1VA | |||
Measurement performance | Accuracy | kWh Class 0.5S | ||
Range | 0~9999999999.99kWh | |||
Clock | accuracy | Error ≤0.5s/d | ||
Active pulse | width | 80±20ms | ||
constant | 1000imp/kWh,10000imp/kWh | |||
Communication | Interface | RS485 | ||
Protocol | MODBUS-RTU | |||
Temperature range | Work | -25ºC~55ºC | ||
Storage | -40ºC~70ºC | |||
Humidity | ≤95%(No condensation) | |||
Altitude | <2000m |
Q: After the meter is powered on, the power or energy count is inaccurate.
A: Switch the meter display to the power (active power P, power factor λ) interface, and check whether the power display is negative or not. And whether the power factor is between 0.9-0.95, and then check whether the incoming and outgoing wires of the current signal wire are connected reversely (that is, the current The incoming wire must be the same as the incoming wire end of the instrument) and consistent with the wiring diagram on the instrument.
Q: The instrument cannot communicate with the host computer normally after power on.
A:1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V;
2. Check whether the communication wiring method is correctly wired in accordance with the wiring diagram requirements (that is, the communication terminal A/B of the corresponding to communication serial port A/B)
ADL | CE |