Rated supply voltage | AC220V |
Rated supply frequency | 50Hz/60Hz |
Contact configuration capacity(A) | 32A,40A,63A,80A Resistive |
Maximum load power | 7kVA(40A),13kVA(63A),17kVA(80A) |
Over-voltage action value | 36G:265V 36T:225~265V(Knob setting) |
Over-voltage reset value | 36G:257V 36T:Over-voltage action value *(97%) |
Under-voltage action value | 36G:175V 36T:165~215V(Knob setting) |
Under-voltage reset value | 36G:180V 36T:Under-voltage action value*(103%) |
Action delay | 36G:0.1S 36T:0.1S~10s(Knob setting) |
Power on delay | 36G:2s 36T:0.3s~30s(Knob setting) |
Reset delay | 36G:1s 36T:0.3s-30s(Knob setting) |
Voltage measurement error | ≤ 1% |
Delay error | ±10%+0.1s |
Knob setting accuracy | ±1V |
Rated insulation voltage | 415V |
IP Class | IP20 |
Class of pollution | 3 |
Electrical Life | 105 |
Mechanical life | 106 |
Altitude | ≤2000m |
Allowable relative humidity | ≤50%(40ºC)(No condensation) |
DIN rail Standard | Width 35mm(IEC/EN60715) |