48V DC 60A 3600W Switch Mode Power Supply Telecom Rectifier System
Specifications for 48V Rectifier System
Model | SPS30-48 /SR4815 | SPS60-48 /SR4830 | SPS90-48 /SR4830 | SPS120-48 /SR4830 | SPS200-48 /SR4850 | SPS210-48 /SR4830 | SPS350-48 /SR4850 |
Rated Output Current | 30A | 60A | 90A | 120A | 200A | 210A | 350A |
Rated Output Voltage | 53.5Vdc (42-58 Vdc) | ||||||
Output Power | 1740W | 3.6KW | 5.4KW | 7.2KW | 11.6KW | 12.6KW | 21KW |
AC Input | |||||||
AC Input Voltage Range | 176~300Vac, 1phase/3wire (@ full load) | 220/230vac 1 ph tolerances: 85~300vac 323~480vac 3ph tolerances: 208~520vac | |||||
AC Input Frequency | 45Hz ~65Hz | ||||||
AC input Power Factor | ≥0.99 | ||||||
AC transfer Efficiency | ≥91% | ≥92% | |||||
AC Input Lightening Protection | NA | 1*50A/2P ClassC SPD | 1*63A/2P ClassC SPD | ClassC SPD | ClassC SPD | ClassC SPD | |
DC Output | |||||||
Output Voltage Range | 42~58 Vdc | ||||||
Current Share | ±5% | ||||||
Load Regulation | ≤0.5% | ||||||
Voltage Regulation | ≤0.1% | ||||||
Environment | |||||||
Operating Temperature | (-20 to 50°C) (Rectifier Temp Range: -45°C to 75°C) | ||||||
Relative Humidity | 5%~95% RH, No Condensation | ||||||
Configuration | |||||||
Rectifier Module | 2*SR4815 | 2*SR4830 | 3*SR4830 | 4*SR4830 | 4*SR4850 | 7*SR4830 | 7*SR4850 |
Controller | 1*CAS-03D (or CAS-02) | ||||||
DC Distribution | 1*30A | 1*60A | 4*32A/1P 4*16A/1P (customizable) | 2*63A/1P 2*32A/1P 2*16A/1P (customizable) | 2*125A/1P (customizable) | 2*125A/1P (customizable) | Customizable |
Battery Breaker | 1*30A | / | 2*63A/1P or 1*100A/1P | 2*100A/1P | 2*125A/1P | 2*125A/1P | 2*125A/1P |
Alarm Relay | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs | 4pcs |
Others | |||||||
Standard | UL60950/EN60950, EN55022, RoHS | ||||||
Communication Port | SNMP, RS232/RS485, Dry contact | ||||||
Subrack Dimension (W*D*H) mm | 482*330*44 (1U) | 482*330*44 (1U) | 482*370*132 (3U) | 482*370*176 (4U) | 482*390*222 (5U) | 482*390*266 (6U) | |
Optional | Wall-mounted | Wall-mounted | DC Lightning Protection | 2nd LVD, DC Lightning Protection | 2nd LVD, DC Lightning Protection | 2nd LVD, DC Lightning Protection | 2nd LVD; DC Lightning Protection |