36kv 40.5kv Embedded Pole for High Voltage Circuit Breaker

Min.Order: 10
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 10

Description
Embedded pole
VEP1-40.5/1250-31.5(VAC802)
VEP1-40.5/1600-31.5(VAC802)
VEP1-40.5/2000-31.5(VAC802)
VEP1-40.5/2500-31.5(VAC802)
 
General description

Get ready to experience the ultimate in reliability and stability with our 36kv 40.5kv High Voltage Embedded Pole for Vacuum Circuit Breaker! This innovative product uses top-of-the-line insulation material to seal the vacuum interrupter and main loop conductive element, as well as the insulation support, resulting in a simple assembly process and a strong tolerance for environmental pollution. 
Designed to be paired with relevant indoor and outdoor vacuum circuit breakers or vacuum distribution devices, our Embedded Pole is perfect for frequent operation places such as electric power, machinery, the chemical industry, metallurgy, mining, and more. With a frequency of 50Hz/60Hz and rated voltage options of 12kV, 17.5kV, 24kV, 27.5kV, and 40.5kV, you can trust that our product will meet all of your high voltage needs. This embedded pole is mainly applied to VZN85-40.5kV series VCB. Meets or exceeds the requirement of IEC60694 and JB-T11203-2011.

Don't settle for less when it comes to reliability and stability. Choose our Embedded Pole for Vacuum Circuit Breaker and experience the ultimate in performance and quality. Get yours today and take your operations to the next level!   
Main technical parameter

Specification of VI

Parameter itemUnitData
Rated voltagekV36/40.5
Rated currentA1250/1600/2000/2500
Rated frequencyHz50/60
Rated short-time power frequency withstand voltage(1min)kV95
Rated lightning impulse withstand voltagekV185
Rated short-circuit breaking current kA31.5
Rated short-time withstand currentkA80
Rated peak withstand currentkA80
Rated short-circuit making currentkA31.5
Rated short-circuit durations4
Rated single capacitor bank breaking currentA400
Rated back to back capacitor bank breaking currentA400
Rated operating sequence O-0.3s-CO180s-CO
Breaking operations of rated short circuit breaking currenttimes20
Mechanical lifetimes10000
Contact automatic closing abilityN120±50
Force required to hold contact open at full strokeN240±50
Circuit resistance at lowest rated contact forceμΩ≤25
Contact limit erosionmm3
Internal gas pressure of vacuum interrupterPa≤1×10-3
Partial dischargePc≤5

Specifications required for matched switchgear
Parameter itemUnitData
Clearance between open contactsmm18±1
Average opening speedm/s1.55±0.15
Average closing speedm/s0.7±0.2
Rated contact pressureN3200±200
Contact bouncing duration at closing operationms≤3
Closing and opening non-simultaneity of contactsms≤2
Maximum rebound during openingmm≤3
Product show

 