Series | Code | Name | Setting range | Manual | Remarks |
0 | SP | Appointed data | Determined by P-SL P-SH | - | 50.0 |
1 | tE | Timing seting | 1~59.59 | please refer to Corresponds to "TE" indicator light | 10 |
2 | AL1 | Temperature alarm | fixed value alarm : Determined by P-SL,P-SH; follow-up alarm: 0.0~100.0 . | please refer to Corresponds to "AL1" indicator light | 100 |
3 | P | Proportion modulus | 0.0~200.0 | When the P↑,the proportion and differential function↑; If the P↓,the proportion and differential function↓ When P=0,the meter is ON/OFF control. | 15.0 |
4 | I | Calculus time | 0~3000S | It's used to adjust static difference. To increse it ,the static difference will be reduced,but if it is too high, the static difference will drift instability. | 240 |
5 | d | Differential time | 0~200S | 30 | |
6 | At | Setting itself function | OFF:close the function ON:open the function | Selection of the Setting itself function | OFF |
7 | t | Control period | 2~120 S | the movements period ON/OFF of Setting relays control is no meaning | 20 |
8 | Hy | Main control by drop in level | 0.1~100.0 | Only have meaning when main control output is ON/OFF(P=0) | 1.0 |
9 | Hy1 | Alarm 1 drop in level | 0.1~100.0 | It has use drop in level setting of alarm contact output | 1.0 |
10 | Pb | Sensor error amendment | ±20.0 | The sensor have deviation can use item to revisal | 0 |
11 | FILE | Filt modulus | 0~50 | It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓ | 20 |
12 | Lock | Code lock | 0~50 | =all the parameter can be revised,or it can't. | 0 |
13 | Sn | Input type | CU50(),PT100(),K(),E(),J(),T(),S(), | CU50(-50~150.0), PT100(-199.9~600.0), K(-30~1300),E(-30~700), J(-30~900),T(199~400), S(-30~1600) | |
14 | P_SL | Display the high limit | P-SL~full range | Can set the high limit displaying input signal | 250 |
15 | P_SL | Display the low limit | Range start ~P-SH | Can set the low limit displaying input signal | 0 |
16 | outH | Allow output max value | OUTL~100.0 | Can output high amplitude limiting, manual and ON/OFF output with no effect | 100.0 |
17 | outL | Allow output min value | 0.0~OUTH | Can output low limit condition, manual and ON/OFF control output with no effect | 0.0 |
18 | ALP | Alarm output definition | 0~1 | '0' upper limit alarm '1' follow-up alarm | 0 |
19 | tEP | Time unit choice | 0~1 | 0:minute and second display 1:hour and minute display | 0 |
20 | COOL | System function choice | ON/ OFF | OFF:reverse control(heating control) ON:positive control(cooling control) | OFF |
21 | oP_R | Output method | - | SSR solid state relay RLP relay output method | RLP |
22 | oppO | Open power output power | 0~100 | Soft start function that meters coefficient after first output of electric power | 0 |
23 | CF | Fahrenheit and degree centigrade selecting | C/F | C:ºC ; F:ºF | C |
24 | dP | Display accuracy | ON/ OFF | 0: have radix point, 1: have no radix point | OFF |
25 | Int | Time function selection | 0~3(Time control side be switched on) | 0:common temperature control 1:start timing when it reaches the temperature,and the built-in buzzer will give an alarm output after reaching the time, the controller keep on heating; 2:start timing when it reaches the temperature,and the built-in buzzer will | 0 |
give an alarm output after reaching the time, the controller stop heating; 3:regular temperature control(no alarm)+time relay function: start timing when the power is on, alarm relay attracting after reaching the time . |