Description
Temperature controller
Intelligence dual row 4-LED diSplay
Operated with 4-key
Control method: On/off, automatic regulation
XMT*7000 series temperature controller are intelligence dual row 4-LED display for displaying the measured value and set value respectively. The temperature meter are operated with 4-keys, allowing an easy inputting. The available control methods include on/off, 2-on/off, PID and automatic regulating and setting controls.
I.Product characteristic
The core of the product adopts the up-to-date microrocessor chip.
Red and green double-bank nixie tube display the measured value and setting value.
Easy operation in the four/three keys, & fast setting in the parameter.
Control in high precision's PID intelligent and two or three bit location check program.
Upper-bank display the measured value, & bottom-bank display the setting value under normal working conditions.
II.Primary technical standard
1.Input: Thermocouple: K,E,J,S
Thermal resistance: PT100 , CU50
2. Range: K(0~400ºC,0~1300ºC),E(0~400ºC,0~800ºC),J(0~1000ºC),
S(0~1600ºC),PT100(-100.0~200.0ºC,0~600ºC),CU50(-50.0~150.0ºC)
3.Measure error: ±0.5%F.S±1byte
4.Silicon control trigger signal(over zero): Range≥3V, Width≥40us
5.The output contact potential of the relay: impedance load AC220V 5A
6.Input power: AC85~242V 50/60Hz
7.Environment: Temperature: 0 to 50ºC, Humidity: ≤85%RH
8.Size: XMT:160×80×125mm hole: 152×76; XMTA:96×96×85mm hole: 92×92;
XMTE:48×96×85mm hole: 44×92; XMTF:96×48×85mm hole: 92×44;
XMTD:72×72×85mm hole: 68×68; XMTG:48×48×110mm hole: 44×44;
Name and functions of the sections(consult)
1)PV display
Indicates the process variable (PV) with a red LED.
(2)SV display
Indicates the setting value (SV) with a green LED.
(3)AT indicator
When auto tuning function is ON, a green LED lights.
(4)ALM1 indicator
When ALM1 output is ON, a red LED lights.
(5)ALM2 indicator
When ALM2 output is ON, a red LED lights.
(6)OUT indicator
When OUT is ON, a green LED lights.
(7)Mode key (SET)
Switches the setting mode and registers the setting value and selected value.
(Setting value and selected value are registered by pressing the mode key.)
(8)Data shift key (<)
(9)Decrease key (∨)
Decreases numeric value of the setting value
(10)rease key (∧)
Increases numeric value of the setting value.
Display Status(consult)
Connection figure(consult)
Setup flow chart
Code | Description | Setting range | Instruction | Remarks |
SP | Setting control point | Whole range | ºC or 1 defined unit | _ |
AL1 | Alarm 1 | Whole range | ºC or 1 defined unit | |
AL2 | Alarm 2 | Whole range | ºC or 1 defined unit | |
SC | Measurement update | -20.0 to 20.0 | Measuring value can be modified through increasing or decreasing this data. Note: It may be cause inaccurate racy of measuring value when you use this function . Please use the function carefully according to your situation. | 0 |
P | Proportional band | 0 to 9999 | When the P↑,the proportion and differential function↑; if the P↓,the proportion and differential function↓. When P=0,the meter is ON/OFF control | 100 |
I | Integration time | 0 to 3000s | It's mainly used to adjust the static difference. To increase it, the static difference will be reduced, but when it is too high, the static difference will drift instability. | 500 |
d | Differential time | 0 to 2000s | When the I↓,the calculus function↑; I↑the calculus function↓. When I=0, no calculus function, it is PD adjustment instrument | 100 |
t | Control period | 1 to 120s | When the d↓,the proportion and calculus function↑; if d↑,the proportion and calculus function↓,but the differential function↑. When d≤t, it has no differential function | 20 |
Hy | Deadband | 0.1to 50.0 | ON/OFF control only | 1.0 |
At | Auto-man | 0 to 1 | 0- Close auto-man function 1- Open auto-man function | 0 |
Lock | Key lock | 0 to 1 | 0- All the parameter can rework 1- Only SP value can rework >1 All the parameter can not rework | 0 |