1000A Class 0.1 Grey Blue High Performance Split Core AC Current Clamp on Cts

Min.Order: 3
Product origin: Beijing, China
Infringement complaint: complaintComplaint
US$ 100

Description

P50 1000A CLASS 0.1 GREY BLUE HIGH PERFORMANCE SPLIT CORE AC CURRENT CLAMP ON CTS


The round jaw design on the P50 Series AC clamp on cts along with the high content nickel metal core makes them well suited for power quality applications where high accuracy and low phase shift along with wide frequency are important. Measurement range is 1mA to 1200A.
The P50 is a general purpose 1000A AC clamp on cts designed for use with DMMs, loggers and other instruments that have a current input. It has a 1000:1 ratio and output of 1mA per amp or 1mV per amp measured in the jaw. The P50 clamp on cts has an integral 2.5m lead terminated. The rounded jaw design on this probe makes it well-suited for power applications where high accuracy 0.1% and low phase shift and wide frequency response are important.

APPLICATIONS

  • Power quality measuring
  • Large industrial loads
  • Measuring around cable bundles
  • Power load monitoring
  • Waveform analysis
  • Energy meter calibrator

FEATURES

  • Measurement range of 1mA to 1200A AC
  • Large jaw opening accommodates conductors up to two 500kcmil
  • Improved ergonomic design and easy operation
  • High content nickel metal core
  • Conforms to EN 61010, 600V CAT III
  • Low phase shift for power measurement
  • Designed for DMMs, recorders, loggers, oscilloscopes, power and harmonic meters
  • UL, CE mark

PARAMETERS

Electrical parameters
Ratio1000: 1 or 2000:1 (customized)
Accuracy class0.1%, 0.2%, 0.5%
Primary current0 - 1000A AC
Secondary output1mV/A  AC, 5mV/A  or (customized)
Max. Cont. Input current1200A
Over voltage categoryCAT III 600V
Output signal333mV, 500mV,1V,2V,5V  AC at nominal input current
Accuracy (1000A Range) 
0-10A≤0.5%
10-100≤0.2%
10-1200A≤0.1%
Phase Shift(1000A Range) 
0-10A≤0.5°
10-100≤0.2°
100-1200A≤0.1°
Electrical parameters - continued 
Frequency range40Hz-2000Hz
Dielectric strength3KV 50Hz/60Hz  at 1 minute
Temperature range-20°C to +55°C
Output2.5 meter cable with D01 connector
Max. voltage not insulated conductors600 V
StandardEN 61010-1, EN 61010-2-032, IEC60044-1 
Installationclamp type
Output modelead output(2.5m)
Mechanical parameters
Dimensions (L x W x H) (mm)102.9 x 219.6 x 28
Weight (g)550
Holding wire diameter (mm)φ50
Max. jaw opening (mm)50
ColorGray or Blue
MaterialPC+ABS+Polycarbonate, UL94 V0
Model Rate CurrentMax CurrentSecondary CurrentCoil RatioBurden ResistanceAccuracy
P50-200200A240A5A40:12.5VA0.5%
P50-300300A360A5A60:12.5VA0.5%
P50-400400A480A5A80:12.5VA0.5%
P50-500500A600A5A100:12.5VA0.5%
P50-600600A720A5A120:12.5VA0.5%
P50-800800A960A5A160:12.5VA0.5%
P50-10001000A1200A5A200:12.5VA0.5%
P501-100100A120A1A100:1customized0.5%
P501-200200A240A1A200:1customized0.5%
P501-300300A360A1A300:1customized0.2%
P501-400400A480A1A400:1customized0.2%
P501-500500A600A1A500:1customized0.2%
P501-600600A720A1A600:1customized0.2%
P501-800800A960A1A800:1customized0.2%
P501-10001000A1200A1A1000:1customized0.1%
P502-500500A600A500mA1000:1customized0.1%
P502-10001000A1200A500mA2000:1customized0.1%
P503-800800A960A400mA2000:1customized0.1%
P503-10001000A1200A400mA2500:1customized0.1%
P504-500500A600A250mA2000:1customized0.1%
P504-10001000A1200A250mA4000:1customized0.1%
Model Rate CurrentMax CurrentSecondary VoltageCoil RatioBurden ResistanceAccuracy
P50V1-10001000A1200A1V1000:1customized0.1%
P50V2-10001000A1200A2V1000:1customized0.1%
P50V4-10001000A1200A4V1000:1customized0.1%
P50V5-10001000A1200A5V1000:1customized0.1%
P50V10-10001000A1200A10V1000:1customized0.1%
P50V1-500500A600A1V1000:1customized0.2%
P50V2-500500A600A2V1000:1customized0.2%
P50V4-500500A600A4V1000:1customized0.2%
P50V5-500500A600A5V1000:1customized0.2%
P50V10-500500A600A10V1000:1customized0.2%


 

Scroll to Top