8-Zone Conventional Fire Alarm Host

Min.Order: 1
Product origin: Shenzhen, Guangdong, China
Infringement complaint: complaintComplaint
US$ 130 ~ 135

Description
8-zone Conventional Fire Alarm Host
Introductions:
1. AW-CFP2166-8 conventional fire alarm panel is designed based on EN54 part 2 & 4 standard.
2. Adopted modularized design, flexible extendable capacity.
3. Two-level control mode by a lock
4.27VDC power supply output.
5. FIRE PROTECTION, FIRE ROUTING and FAULT signal output, the output can be configured to dry relay type or wet sources type.
6.2 channel general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. SILENCE button to stop BUZZER and SOUNDERS.
11. EVACUATE button to start a manual fire alarm immediately.
12. TEST button to test all LEDs orderly.
13. Low-battery protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
14. Optional GSM module is available for fire alarm by SMS.
Freeman Zhou
GSM: 008613922805315

Asenware, professional fire alarm solution provider.
ITEM
1Zone panel
2Zone panel
4-8 Zone panel
12-32 Zone panel
Model No.
AW-CFP2166-01
AW-CFP2166-02
AW-CFP2166-04-8
AW-CFP2166-12-32
Power specification


Mains supply voltage
110VAC or 240VAC
Internal power supply
27.2VDC
Total output current limited
500mA @ 240VAC
500mA @ 240VAC
3A @ 240VAC
3A @ 240VAC
Main supply monitor for fault
Yes
Battery protection for low voltage
Yes
Batteries (default configuration)
12V2AH*2
Detector circuit specification


Number of circuit
1
2
4-16
4-32
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Line fault monitor for detector removal
Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device
6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Detector continuity diodes
Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value
470 to 680 Ω, 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone
20 (based on a total detector current of 2mA, each detector consuming 100μA).Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zone
No limit
Sounder circuit specification


Number of general circuits
2
End of line resistor value
6.8k Ω,5% tolerance, 0.25W (colour code-blue,grey,red,gold)
Line fault monitor for open circuit
Yes
Line fault monitor for short circuit
Yes
Outputs fused AT
400mA
Maximum number of bells @ 20mA of each sounder output
20
Fuses


Battery fuse
1.5A F 20mm
Sounder outputs
500mA F 20mm
Fire and fault output


Output type
NC and NO relay
Maximum current
100mA
Connection block


Largest acceptable conductor size
2.5mm2
Smallest acceptable conductor size
0.75mm2
Size and weight




Dimensions(mm)
272*200*70mm
320*231*90mm
395X502X124
362X565X124
Weight (without batteries)
4kg
5kg
7kg
8kg
Weight (with batteries)
5.8kg
6.8kg
9.6kg
12.5kg
Scroll to Top