Features: ECS1030 is split core current transformers. This CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. Can be mounted without removing existing cables for easier installation.
Specifications: Rated Primary Current(Amp.) 50/60Hz 30nom(0.1~60A max) Turn Ratio Np:Ns=1:2000 Current Ratio 30A/15mA D.C. Resistance at 20 ºC 250Ω Accuracy @RL<=10Ω 0.5% Linearity @RL<=10Ω 0.5% Phase error at rated current range <=1.6˚ Operating Temperature Range -40~65ºC Storage Temperature Range -45~85ºC Dielectric Withstanding Voltage(Hi-pot) 2.5KV/1mA/1min Insulation Resistance DC500V/100MΩ min
Certificates: UL Recognized / CE certificated / RoHs
Warranty: 5 years
Customized current ratio available:
Model
Input Current
Outputs
ECS10-15
15A
current outputs @ 20mA, 33.3mA, 40mA, 50mA, 100mA, 1A voltage outputs @0.25V, 0.333V, 0.5V, 1V, 2V