Product Name:2 Loops Addressable Fire alarm System Fire Alarm Control panelMain power supply:AC220V± 15%, 50HZ.
Battery power supply:DC 24V (2 sealed batteries: 2*12V*4Ah)Product capacity:2 loops*254 points = 508 points
Loop capacity:Up to 254 points in any combination of 2-wire
smart smoke detector, heat detector, call point, input module,output module and sounder.
Direct output:6 groups of wet contacts relay output.
Contacts capacity :1A/24VDC, output current 500mA. Battery power output: 1 group 24V power output Output
capacity:1A/24V. Operating Environment:Temperature -10°C~+50°C Humidity ≤95%.
 Dimensions: 450mm×370mm×120mm. Product standard: GB4717-2005, GB16806-200.

2 Loops Addressable Fire alarm System Fire Alarm Control panel



Appearance and dimensions:



System composition

Chassis
Function module8600.1 master board (with LCD)
8600.2 power board
8600.4 Master and Bus Control Keypads
8600.5 direct linkage control panel
8600.6 loop board
8600.7 linkage output board
Micro printer
Power supply:24V switching power supply 100W, Battery2*12V*4Ah

 Main functions:

1 System self-test

The system will test indicator light,LCD screen,sound and so on.

2 Inquiry function

You can see the device type, zone number, definition about whether there are devices, position information corresponding to each address in the loop.

3 Event record

Under this menu, you can see the fire alarm information and other operation record.

4 Data sampling

Data sampling can sample the products in the loop, and displayed as data. The data can be used to judge the status of the products.

5 Setting function

In this function, you can set the password, time and the printer.6 Installation and program functions

(1) Address coding: the control unit can read or write the product address.

(2)Login: Connecting the products to the control unit. Auto login can login the address and type of the products.

(3)Logic programming: Set the logical relationship between the product and the control unit. Including system linkage, bus linkage and direct linkage.

7 Feedback function

The control unit will display the feedback information after start the equipment manually or automatically and send the alarm sound, lights up the feedback light. Feedback is real information about the starting of fire-fighting equipment.

8 Faulty alarm function

The control unit can automatically check the working status of main power supply,battery power supply detectors and modules. If the control unit found any abnormal address during the inspection process, after many confirmations, it immediately reported the fault information of the control unit number, loop number, and address number. The "faulty" indicator light is on, and you can hear the faulty sound. Press the "mute" key to mute.