Description
The H-CT005 Series are split-core current transformers. The CT can be mounted to existing panels, such as control centers or load centers, to measure or monitor wattage. These current transformer's can be mounted without removing existing cables for easier installation.
1, Electrical Specifications
1), Rated Primary Current(AMP. ) 50/60Hz: 250nom(1~250A max)
2), Turn ratio: Np: Ns=1: 50
3), Current Ratio: 250A/5A
4), D. C. Resistance at 20 º C: 1.5Ω MAX
5), Accuracy @RL=1VA: 0.5%
6), Phase error at rated current range: ≤ 0.5°
7), Operating Temperature Range: -40~70º C
8), Storage Temperature Range: -45~85º C
9), Dielectric Withstanding Voltage(Hi-pot): 3.5KV/1mA/1min
10), Impulse Withstand Voltage: 5KV Peak
11), Insulation Resistance: DC500V/100MΩ Min
2, Applications.
A, Portable/Curret instruments.
B, Sub-metering.
C, Monitor Motor Loads
3, Feature
A, Small size.
B, Low cost
C, High secondary turns.
D, Secure locking hings
E, Full RoHS compliant
F, Mounting easy.
4, Material List:
NO
ITEM
DESCRIPTION
UL Card
MATERIAL
NOTE
1
CORE
UU53
/
SILLICON STEEL
2
CASE
PP3307
E235269
PP
3
BOBBIN
D202G15@
E107536
PBT
4
WIRE
2UEW
E164502
UEW/U
5
LEAD WIRE
UL1007 16AWG
E189674
PVC
80º C 300V
6
SOLDER
99.3%Sn0.7%Cu
/
Sn