Suin SA2200 Portable Power Quality Analyzer IEC61000-4-30 Class A

Min.Order: 1
Product origin: Shijiazhuang, Hebei, China
Infringement complaint: complaintComplaint
US$ 2352 ~ 2548

Description
Overview
SA2200 Power Quality Analyzer is the professional potable device to measure and analyze the power system quality, supply the harmonics analysis and power quality data analysis, also provide big memory for the data storage, which is used to make the long term logger measuring to power system.

Design Features

Class A compliance under international standards

Basic voltage measurement accuracy of±0.1%

Special waveform record function

200kS/s sample rate

Support multi language

32GB micro SD card

GPS time synchronization

Product Shows 

Specification
Channel(Voltage/Current)4/4
Voltage Range1-1000Vrms, 6000V transient voltage
Current Rangedepends on supplied current clamp
PC software analysisYes
Micro SD card(bulid-in)32GB
BatteryLithium ion, 5200mAh/>8h
Time SynchronizationGPS/Beidou(option)
interfaceUSB Host, LAN, WIFI
WIFI App(option)
Screen5.6' TFT LCD with resolution640*480(SA2200)
Language14-Chinese, English, French, German, Italian, Japanese, Korean, Polish, Portuguese(Brazil/Portugal), Russian, Spanish (Latin/Spain), Turkish
Dimension/Weight       270*190*66mm/2.0kg
Wire Combinatios           1Ø+NEUTRAL,1Ø SPLIT PHASE,1Ø IT NO NEUTRAL,3Ø WYE,
 3Ø DELTA, 3Ø IT, 3Ø HIGH LEG, 3Ø OPEN LEG, 
2-ELEMENT, 2 1/2-ELEMENT
Electrical SafetyIEC61010-1 ,Safety Degree: 600V CAT IV    1000V CAT III
Measurement
Voltage/Current/FrequencyMeasurement RangeResolutionAccuracy
Vrms(AC+DC)1 ~ 120Vrms0.001Vrms±0.1% of nominal voltage
120Vrms~400Vrms0.01Vrms
400Vrms~1000Vrms0.1Vrms
Vpk1 ~ 1400Vpk0.01Vpk±0.5% of nominal voltage
V(Crest Factor)1.0 ~ >2.80.01±5%
Arms(AC)       10mV/A0~150A0.01A±0.1%±0.1A
       1mV/A1~2000A0.01A±0.1%±0.1A
       65mV/1000A 10~6000A0.01A±0.1%±0.2A
A(Crest Factor)1 ~ 100.01±5%
Frequency42.5~57.5(50Hz nominal)0.01Hz±0.01Hz
51~69(60Hz nominal)0.01Hz±0.01Hz
320~480(400Hz nominal)0.01Hz±0.01Hz
Dips & Swells
Vrms1/20 ~ 200% of nominal voltage 0.01Vrms±0.2%
Arms1/2depends on current clamps0.01A±1% 
Harmonic (IEC61000-4-7)
Harmonic Number1 ~ 100(50/60Hz) (IEC61000-4-7)   1~12(400Hz)
Harmonic Voltage %f0.0 ~ 100.0%0.01%±0.1% ± nx0.1%
Harmonic Current %f0.0 ~ 100.0%0.01%±0.1% ± nx0.1%
THD0.0 ~ 100.0%0.01%±2.5%
Phase-180° ~180°0.1°± nx0.1°
Power and Energy
P, S, Q1Max. 6000MW0.1kW±1%±10 digits
PF & cosФ0 ~ 10.01±0.01
kWh, kVAh, kvarhdepends on nominal voltage and current clamps±1%±10 digits
Flicker (IEC61000-4-15)
Pst(10min)/Plt (2 hrs)0.00 ~ 20.000.01±5%
Unbalance
Voltage0.0 ~ 20.0%0.10%±0.1%
Current0.0 ~ 20.0%0.10%±1%
Voltage Phase-360° ~ 0°0.1°±0.1°
Current Phase-360° ~ 0°0.1°±0.5°
Voltage Transient
Vpk±6000Vpk0.01V±15%
Vrms10 ~ 1000Vrms0.01V±2.5%
Min. Test Time5us
Inrush Current
Armsdepends on current clamps0.01A±1% ± 5digits
Inrush Duration1 ~ 32min selectable10ms±20ms
Mains Signaling
Signaling Frequency60-3000Hz0.1Hz 
Relative V%0%-100%0.10%±0.4%
Absolute V3s (3s average)0.0-1000V0.1V±5% of Nominal voltage
Logger
Recordinguser-defined parameters for 4 phases at the same time
MemoryData stored in Micro SD card, 32GB
Duration Time2 hrs to 1 year, depends on the recording items and time interval
Interval1s to 60 minutes
Monitor
Support EN50160 in default or user-defined standard
 
Options

About SUIN
Shijiazhuang SUIN Instruments Co., Ltd is a high-tech company and concentrates on R&D, production, test, sales and service of test & measurement instruments, electrical products, application software, etc.



Product Tag:
Related categories:
Scroll to Top