4000 Liter Per Hour Water Treatment and Reverse Osmosis Machine

Min.Order: 1
Product origin: Wenzhou, Zhejiang, China
Infringement complaint: complaintComplaint
US$ 1200 ~ 30000

Description
4000 Liter Per Hour Water Treatment and Reverse Osmosis Machine

How the Reverse Osmosis System Works

Reverse Osmosis is a process in which dissolved inorganic solids (such as salts) are removed from a solution (such as water). This is accomplished by pressure of high pressure pump pushing the water through a semi permeable membrane. The membrane (which is about as thick as cellophane) allows only the water to pass through, not the impurities or contaminates. These impurities and contaminates are flushed down the drain.
Ultimately, the factors that affect the performance of a Reverse Osmosis System are:
Incoming water pressure
Water Temperature
Type and number of total dissolved solids (TDS) in the water
The quality of the filters and membranes used in the RO System (see operating specs)

How to Select the Right Reverse Osmosis System
Crane Environmental has the most complete line of Reverse Osmosis equipment in the industry. To select the right Reverse Osmosis system for your application, there are four primary considerations; the type of raw water, the quality of the product water required, the capacity of product water required, and any special features such as storage, repressurization, or mounting. 
 
Technical route and flow diagram instructions 
The technical route is as following.
Raw tank-->Booster pump -->Quartz sand filter-->activated carbon filter--->Anti-scalant
dosing-->Sediment filter-->High pressure pump-->RO desalination device-->Permeate tank
 
Features
Materials of Construction 
Skid Frame: SS304 
Membrane Elements:
HYDRANAUTICS  CAP3-8040
Membrane Housings: SS304
Low pressure piping: SS304
High pressure piping: SS304 
Pump and Motor 
Pump: 304SS vertical multi-stage centrifugal 
Motor: TEFC, 380/460 VAC, 3-phase, 50/60 Hz. 
Standard Features 
8" x 40" High rejection membrane elements 
5-micron sediment pre-filter housing 
Automatic inlet solenoid valve 
PLC control
Product water conductivity monitor 
Operating pressure gauges 
Product and concentrate flow meters 
Concentrate and recycle flow control valves 
Low inlet pressure switch with shutdown alarm 
Auto/Manual wash 

Optional Equipment Available 
Atmospheric storage tanks with level control and repressurization pump 
Pressurized storage vessels 
UV
Ozone generator
Membrane clean-in-place (CIP) systems 
Pretreatment chemical injection systems 



Model  NoWT-RO-4000
Capacity4000LPH(Liter per Hour)
Nominal Recovery65-75%
Nominal Salt Rejection99.60%
Operating Temperature1 5°C -4 5°C
Design Temperature25°C
Feed Pump 1.10KW
High Pressure Pump 5.50KW
Voltage 2 2 0V  / 380V / 460V - 50Hz / 60Hz 