GF333 Multifunction AC DC Digital Meter Calibration Electrical Equipment

Min.Order: 1
Product origin: Beijing, China
Infringement complaint: complaintComplaint
US$ 3000 ~ 6500

Description
GF333 Multifunction AC DC digital meter calibration electrical equipment
Product Description

 


GF333 can be used as a calibration device standard meter, also as a testing calibrator in measurement test center of grid corporation, power company and measurement department in power plant, national levels of measurement mechanism, quality inspection departments, research institutes, tertiary institutions, industrial and mining enterprises, electric energy meter and electrical instrument production enterprises etc.
Features
Measure the AC voltage, current, active power, reactive power, frequency, phase angle and power factor etc;
Measure the AC voltage, current 2~31 harmonic content and waveform distortion degree;
Measure active power energy error, reactive power energy error, the maximum output pulse frequency is to 2 MHZ;
Measure calibration device of voltage, current, power stability;
Measure calibration device the standard deviation of estimate;
Measure the voltage of the calibration device three-phase symmetric degrees, the current of three three-phase symmetric degree;
Measure calibration device of the magnetic induction;
Measure DC voltage and DC current;
Transducer measurement;
With RS232 interface, it can be controlled by PC operation;
Core part uses the 32 bit DSP and16 bit low power and high speed DAC consists of high accuracy AC collector.
Using 6.5 inch TFT color LCD screen, character display clear chart. Have the advantages of wide measuring range, high precision, stable and reliable operation, simple operation etc.
Product Parameters

 

Electrical parameters
Accuracy class 0.02%, 0.05%
Power supplyAC 220 V±10% or 110 V±10%, 50/60Hz
Power consumption<30VA
Warming-up time<30min
Voltage measurement
U1, U2,U36.25V, 12.5V, 25V, 50V, 100V, 200V, 400V, 800V (switch automatically), max 1000V
Range(0-120%)RG
Resolution0.01%RG
Accuracy0.02%RD or 0.05%RD
Current measurement
I1, I2, I30.25, 0.5, 1, 2.5, 5, 10, 25, 50, 100A(switch automatically)
Range(0-120%)RG
Resolution0.01%RG
Accuracy0.02%RD or 0.05%RD
Power measurement
Active accuracy0.02%RD or 0.05%RD
Reactive accuracy0.05%RD or 0.1%RD
Apparent accuracy0.02%RD or 0.05%RD
Energy measurement
Active accuracy0.02%RD or 0.05%RD
Reactive accuracy0.05%RD or 0.1%RD
Phase measurement
Range0.00°-359.99°
Resolution0.001°
Accuracy0.02° (voltage ≥50V and current ≥250mA)
Frequency measurement
Range45-65Hz
Resolution0. 001Hz
Accuracy0.002Hz
Power Factor measurement
Range-1.0 ~ 0 ~ +1.0
Resolution0.0001
Accuracy0.0005
Electric energy pulse output 
Pulse constant range1-2880000000
Output frequency of max. pulse600 kHz
Load capacity>2mA
Default pulse output frequency10kHz-600kHz
Energy pulse Input
Input range of pulse constant600-700000
Setting range of test pulse1-999999999
Max. pulse receiving frequency2MHz
Pulse input level5V
Voltage/current harmonics measurement
Times2-31
Error0.05%
Distortion degree error0.05%
Transducer measurement
DC voltage range±1, ±5, ±10, ±20 V
Accuracy0.01%
DC current range±1, ±2.5, ±5, ±10, ±20mA
Accuracy0.01%
Ripple error1%
DC measurements (option)
DC voltage50V, 100V, 200V, 400V, 800V (switch automatically), max 1000V
Range(0 -120%) RG
Resolution0.01% RG
Accuracy0.02% RD
DC current0.1A, 0.3A, 1A, 3A, 10A, 30 A(switch automatically)
Range(0-120%) RG
Resolution0.01% RG
Accuracy0.02% RD
Mechanical parameters
Dimensions (W×H×D) (mm)440×360×160
Weight (kg)10
Environmental conditions
Operating temperature10°C to 30°C
Relative humidity≤85%
Detailed Photos

 