Widely used in Cooling/Heating (with Hot Water supply) projects of large/small industries & civil building. For example, large hotels, guesthouse, health centers, schools, entertainment centres, bath centers, and so on. Especially sites with higher requirement on noise and surrounding environment, sites that not allow the installation of the boiler, also sites which are not easy to install cooling tower. RMRB HEAT PUMP will be your best choice.

1)Module intelligent central controller, automatically monitor the machine, reliable performance;
2)Air conditioning ( cooling, heating ) and hot water integrated design, select different modes in different seasons, high energy saving performance, simple installation, drop investment;
3)Scroll type for famous Copeland compressor, stable use;

This Model RMRB-25S-2D:
1)Rated refrigeration quantity 66kw, Heat recovery 68kw,
Rated heating output 86kw, Rated output water quantity 1800L/h
2)Rated heating input power 21kw, rated refrigeration input power 20.5kw.
3)Voltage 380V ~420v / 50Hz or 60Hz
4)Hot water temperacture 55-60º C
5)Cold water return temperature 12º C

Others:
Weight Packed: within 780kg, Size: 1810*1100*1920 mm.
Control Mode: Microcomputer central processor (linear control)
Protection Function: High pressure protection, low pressure protection, phase failure, reversed phase, water current switch, overpower protection, freeze protection
No pollution to the environment, it is the world's highest energy saving and environment protective product within the air conditioner and water heater range.

Item / Model
RMRB-15S-2D
RMRB-10S
RMRB-20S
RMRB-25S
Heating output(KW)
43.3
32
66.2
79.5
Cooling capacity(KW)
37.3
24.5
48.7
60.5
Heat recovery heating(KW)
40
26.8
50.5
61.5
Rated hot water output(L/h)
1000
630
1340
1640
Heating input power(KW)
13.3
8.5
18
22
Cooling input power(KW)
13.2
9.2
19.2
22.3
Throttling way
thermal expansion valve
Working pressure(M Pa)
0.8~1.2
Unit noise(dB)
≤65

Unit weight(Kg)(packed)
Within 400
Within 286
Within 630
Within 780
Power supply
380V/3N~/50HZ
Power cable
R
Cross-sectional area
6
10
16
25
The number of
3
3
3
3
N
Cross-sectional area
2.5
6
6
6
The number of
1
1
1
1
G
Cross-sectional
6
10
16
16
The number of
1
1
1
1
Hot water side select pump parameters
Flow m³/h
3.8
7.8
15.6
20.3
Lift m
≥8( Depend on site )
>8
Power W
*
*
*
*
AC side select pump parameters
Flow m³/h
3.2
7.4
14.8
18
Lift m
≥25( Depend on site )
>8
Power W
*
*
*
*