Model | Heat Rejection Capacity | Fan | Pump | Operation Weight | ||||
Fan | Air Volume | Power | Qty. | Water Volume | Power | |||
Rton | m³/h | KW | m³/h | KW | KG | |||
KCF-15 | 15 | 1 | 1*20000 | 1*0.75 | 1 | 1*28 | 1*0.75 | 3260 |
KCF-25 | 25 | 1 | 1*28000 | 1*1.5 | 1 | 1*28 | 1*0.75 | 3280 |
KCF-35 | 35 | 1 | 1*28000 | 1*1.5 | 1 | 1*28 | 1*0.75 | 3400 |
KCF-45 | 45 | 1 | 1*40000 | 1*3.0 | 1 | 1*28 | 1*0.75 | 3540 |
KCF-58 | 58 | 1 | 1*45000 | 1*4.0 | 1 | 1*28 | 1*0.75 | 3700 |
KCF-70 | 70 | 1 | 1*40000 | 1*3.0 | 1 | 1*53 | 1*1.1 | 3410 |
KCF-85 | 85 | 2 | 2*35000 | 2*2.2 | 1 | 1*53 | 1*1.1 | 5300 |
KCF-100 | 100 | 2 | 2*35000 | 2*2.2 | 1 | 1*53 | 1*1.1 | 5490 |
KCF-110 | 110 | 2 | 2*45000 | 2*4.0 | 1 | 1*53 | 1*1.1 | 5530 |
KCF-125 | 125 | 3 | 3*28000 | 3*1.5 | 1 | 1*70 | 1*1.5 | 9030 |
KCF-140 | 140 | 3 | 3*45000 | 3*4.0 | 1 | 1*70 | 1*1.5 | 9120 |
KCF-155 | 155 | 3 | 3*35000 | 3*2.2 | 1 | 1*84 | 1*2.2 | 10180 |
KCF-165 | 165 | 3 | 3*40000 | 3*3.0 | 1 | 1*84 | 1*2.2 | 10210 |
KCF-185 | 185 | 3 | 3*45000 | 3*4.0 | 1 | 1*84 | 1*2.2 | 10550 |
KCF-200 | 200 | 4 | 4*35000 | 4*2.2 | 1 | 1*150 | 1*3.0 | 11250 |
KCF-220 | 220 | 4 | 4*45000 | 4*4.0 | 1 | 1*150 | 1*3.0 | 11330 |
KCF-235 | 235 | 4 | 4*45000 | 4*4.0 | 1 | `1*150 | 1*3.0 | 11930 |
KCF-260 | 260 | 4 | 4*40000 | 4*3.0 | 1 | 1*180 | 1*4.0 | 14730 |
KCF-275 | 275 | 4 | 4*40000 | 4*3.0 | 1 | 1*180 | 1*4.0 | 14730 |
KCF-290 | 290 | 4 | 4*45000 | 4*4.0 | 1 | 1*180 | 1*4.0 | 14770 |
KCF-315 | 315 | 4 | 4*45000 | 4*4.0 | 1 | 1*180 | 1*4.0 | 15370 |
KCF-335 | 335 | 5 | 5*40000 | 5*3.0 | 1 | 1*233 | 1*5.5 | 18430 |
Note: the 'Rated Capacity' based on standard condition: water inlet and outlet temp. 37-32degC, wet bulb temp. 28degC. |